Technical Data
Instruction handbook
b maXX
BM5500, BM5600, BM5700
Document No.: 5.13008.10
105
3
3.5.3
Electrical data BM554X power module
BM554
3
-
XXX
8
BM554
4
-
XXX
8
BM554
5
-
XXX
8
BM554
6
-
XXX
8
Rated input power
1)
41 kW
50 kW
64 kW
84 kW
Rated input current
1)
(I
eff
)
76 A
93 A
119 A
155 A
Max. input current (I
eff
)
113 A
120 A
155 A
207 A
Rated DC link voltage
1)
(U
DC
)
540 V
DC
DC link capacitance (internal)
1880
F
2350
F
3055
F
3760
F
DC link discharging time (internal DC link capaci-
tance)
45 s
55 s
70 s
90 s
Output voltage
1)2)
(U
AC
)
3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
9)
0 Hz to 450 Hz
Rated output current
1)4)5)6)11)
(I
AC
)
at 4 kHz
3)
80 A
100 A
130 A
150 A
Rated output current
1)4)5)6)11)
(I
AC
)
at 8 kHz
3)
75 A
72 A
94 A
105 A
Output peak current
1)4)6)7)11)
(I
AC
)
at 4 kHz
3)
120 A
130 A
170 A
200 A
Output peak current
1)4)6)7)11) (
I
AC
)
at 8 kHz
3)
90 A
94 A
130 A
150 A
Max. peak current period
7)
60 s
Power loss referring to the power input
800 W
1000 W
1300 W
1400 W
Power loss referring to the control voltage
112 W
Power loss of the device fan
referring to 230 V
AC
8)
87 W
Current of the integrated brake control
Max. 8.0 A
10)
Cooling air requirement power heatsinks
260 m³/h
210 m³/h
Cooling air requirement internal space
60 m³/h
.
1)
All rated values refer to a DC link voltage of 540 V
DC
and a control voltage of 24 V.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U
AC
3 0 V to
3
U
DC
2
-----------
10 V
–
=
without overmodulation of the PWM.
3)
Switching frequency of the inverter (adjustable).
4)
RMS at an environmental temperature of 40 °C.
5)
The input current must be reduced between 40 °C and 55 °C. Refer to correction factors at changed operating conditions