Technical data
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
47
3
3.3.4
Required environmental conditions
Transport temperature range
- 25 °C to + 70 °C
Transport climate class (K)
EN 60721-3-2
2 K 3
Storage temperature range
- 25 °C to + 55 °C
Storage climate class
EN 60721-3-1
1 K 4
Operating environment
BM50XX
BM517X
BM519X
Industrial supply network C2
Industrial supply network C3
1)
,
refer to
Industrial supply network C3
Operating temperature range
Min. 5 °C to max. 55 °C
(with derating above 40 °C)
2)
Operating climate class
EN 60721-3-3
3 K 3
Installation altitude
Up to 4000 m above MSL
(with derating above 1000 m)
2)
Humidity (operating)
EN 60721-3-3
Relative humidity: 5 % to 85 % non-condensed,
and
absolute humidity: 1 g/m
3
to 25 g/m
3
Ionizing and non-ionized radiation
< measurable range
Vibration, shock and continuous shock
EN 61800-5-1, chapter 5.2.6.4 vibration test
Max. 0.5 g when operating
Degree of contamination
EN 61800-5-1, table 6, tab. 2
2
1)
If used in areas according to the category C2 of IEC 61800-3:2012, additional measures might be necessary. In this case the plant
manufacturer / user has to provide evidence these additional measures take effect and the in IEC 61800-3 required thresholds of the
category C2 are met.
2)
Refer to correction values at changed operation conditions at
Correction values at changed operating conditions
NOTICE!
Normally only a non-conductive dirt buildup occurs. Any conductive dirt buildup,
whether short-term or permanent, is prohibited and could lead to destruction of the
device. The customer is responsible for destruction resulting from dirt buildup of con-
ductive materials or matter.