Installation
Instruction handbook
b maXX
5000
Document No.: 5.09021.16
131
7
m
Grounding concept, PE-connection from device to device, cooling type S
Power supply
PE bar
Figure 56:
Grounding concept, PE connection from device to device
1
(Active) mains rectifier unit
2
Single axis unit 75 mm
3
Single axis unit 50 mm
4
Double axis unit 50 mm
5
Double axis unit 75 mm
6
Mounting plate, thickness at least 3 mm
NOTE!
The first
and
last device must be connected
directly
with PE if the PE connection is
realized from device to device. An accessories kit is available for the connection from
device to device, see
Accessories kit PE connection from device to device
page 287, part No. 467439.