Technical Data
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
31
3
3.3.6.2 Environmental temperature
The devices
BM3200, BM3300
are provided for an environment temperature of
T
rated
= 40 °C. At usage in environments with a deviating temperature between 40 °C and
55 °C the permitted output current (I
O
) is to be calculated according to the following for-
mula:
The coolant temperature corresponds to the environmental temperature.
3.3.6.3 Supply voltage
3-phase operation
above rated
supply voltage
The rated voltage is 3 x 400 V
At supply voltages above the rated supply voltage, the output current is to be reduced at
constant output power, accordingly.
Figure 8:
Output current dependent on supply voltage
NOTE!
It is no derating necessary while single phase operation of a three phase device
BM3201
-X
T
,
BM3301X
-X
T
.
I
O
I
O
40°C
1
Coolant temperature
- 40°C
°C
---------------------------------------------------------------------------------------
0 03
–
=
Output volt
ag
e de
vice
Supply voltage
180 V
400 V
528 V
100 %
50 %