Parameter
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
33
4
Refer to following calculation for protection level and warning level.
1
Protection level (error level)
= V
+10
* (R
PTC1
//47k) / [R1 + (R
PTC1
//47k)]l
2
Warning level
= V
+10
* (R
PTC2
//47k) / [R1 + (R
PTC2
//47k)]
3
Definition:
V
+10
:
voltage b10V-ACM, range 10.4 to 11.2 V
DC
R
PTC1
:
motor PTC overheat protection level.
Corresponding voltage level set in
R
PTC2
:
motor PTC overheat warning level.
Corresponding voltage level set in
47k:
is AVI input impedance
R1:
resistor-divider (recommended value: 1 to 20 k
Ω
)
Take the standard PTC resistor as example:
If protection level is 1330
Ω
, the voltage b10V-ACM is 10.5V and resistor-divider
R1 is 4.4k
Ω
. Refer to following calculation for
setting.
1330//47000 = (1330*47000)/(1330+47000) = 1293.4
10.5*1293.4/(4400+1293.4)=2.38(V)
≈
2.4 (V)
Therefore,
should be set to 2.4.
Figure 10:
PTC resistor curve
P0120
Warning level PTC overheat, refer to
P0121
Reset level PTC overheat, refer to
P0120
Motor Kaltleiter Überhitzung Warnungsgrenze
0.1 to 10.0 V
EE
Motor PTC overheat warning level
1.2 V
ON
BM_u_PTCOverheatWarningLevel
10:1
-
P0121
Motor Kaltleiter Überhitzung
0.1 to 5.0 V
EE
Motor PTC overheat reset delta level
0.6 V
ON
BM_u_PTCOverheatResetLevel
10:1
-