Parameter description
Parameter manual
b maXX
®
1000
Document no. 5.07004.03
Baumüller Nürnberg GmbH
124
4.3
P1211
A setting of 100% is equal to the rated output current of the drive.
During acceleration, the b maXX
®
1000 output current may increase abruptly and exceed
due to rapid acceleration or excessive load on the motor.
When this function is enabled, the b maXX
®
1000 will stop accelerating and keep the out-
put frequency constant until the current drops below the maximum value.
Figure 54:
Over-current stall prevention during acceleration
Value
Meaning
0.0
Disabled: over-voltage stall prevention with brake unit or brake resistor
330.0 to 410.0 V
DC
230 V device for 230 V mains voltage
660.0 to 820.0 V
DC
460 V device for 460 V mains voltage
P1211
Überstrom Abschaltschutz während Hochlauf
0 to 250 %
EE
Over-current stall prevention level during accel-
eration
170 %
STOP
BM_u_OverCurrentStallPreventionLevelAccel
1:1
Value
Meaning
0
Disabled
20 to 250 %
Enabled