Commissioning/Operation
Instruction handbook
b maXX
(BM4-F-)AIO-XX (Analog IO module)
Document No.: 5.01045.08
49
8
8.2.2
Testing of the Analog IO module
Once the plug-in module has been recognized properly, then it can be checked whether
the input and outputs are working correctly using ProDrive.
Pre-conditions
Basic unit
b maXX
BM4000
has been commissioned,
BM4-F-AIO-XX
has been plugged in or
AIO-XX
is available (ES controller).
Analog connections are available/connected and ready for use (pin assignment see
on page 39), in addition:
m
AIO-01, AIO-02, AIO-03
Voltage range of +/-10 V
DC
can be set by a potentiometer.
m
AIO-04
Current range of 0 ... 20 mA can be set by a current calibrator
Motor for speed set (clockwise or counter-clockwise) has been connected; shaft ends are
rotating freely.
h
ProDrive Navigation „Diagnosis“, submenu „Service“.
h
Check in the menu „Service“, whether the
Analog-IO-Module
has been correctly rec-
ognized, e.g. in the line for the
slot
D
NOTICE!
Notice electrostatic discharge
The
BM4-F-AIO-XX
or the
b maXX
BM4000
may get damaged if the module is
plugged or pulled out when the
b maXX
BM4000
is energized.
If the plug-in module has still to be pulled out from the
b maXX
BM4000
due to an
external action, switch off the
b maXX
BM4000
.
Try then to push in the
Analog IO module
again as described in the chapter
Restart the
b maXX
BM4000
again
and check for errors/error messages.