6
|
Electrical installation
Baumer Hübner
36
Operating Manual
HMG10 & HMG10P DeviceNet | V1, T1
1
4
5
2
3
Ill. 10:
Connecting the supply cable
1
Torx / slotted screw M4x32 mm
2
Terminal box cover
3
Cable gland M20x1.5 mm for cable di-
ameter 5...13 mm
4
Connection terminals (wire cross-sec-
tion ≤ 1.5 mm
2
5
Cable shield
Tool
n
20 mm
n
22 mm
Instruction:
a) Loosen the screws at the terminal box.
b) Lift the terminal box off the encoder.
c) Loosen the cable gland at the terminal box.
d) Insert the supply cables into the cable gland, let stick out approx. 50 mm of cable.
e) Connect cable shield to cable gland and make sure it covers a large area.
f) Assign the supply cables to the terminals.
g) Attach the cable gland to the terminal box.
h) Mount the terminal box at the encoder. To do this, tighten the screws with a torque of 2-3
Nm.