8 Heartbeat Service
8.1
General
The device supports a heartbeat producer according CiA 305.
Example for a heartbeat protocol:
COB-ID
Data/Remote
Byte 0
701h
D
7Fh(127d)
The heartbeat messages consist of the COB ID and one byte. In this byte, the NMT status is supplied.
0:
BootUp-Event
4:
Stopped
5:
Operational
127:
Pre-operational
In other words, the sensor is in the pre-operational mode (7Fh = 127).
8.2
COB-ID
The COB-ID for the heartbeat message is 700h + node ID.
8.3
Timing
The minimal cycle time for heartbeat messages is 10 ms.