5.7. Implementation of system functions for alarm handling
Make sure that the system components required for alarm handling have been implemented in the project.
These are in particular OB82 ("I/O Point Fault") and OB86 ("Loss Of Rack Fault"). If these components are
missing the PLC will enter state STOP in case of an alarm.
5.7.1. I/O Point Fault OB (OB82)
The supported channel-specific diagnostic alarms are described under 4.7.1
„I/O Point Fault OB“ in the
related chapter of Step7
®
.
5.7.2. Loss Of Rack Fault OB (OB86)
Loss of Rack Fault OB (OB86)
is triggered when the encoder is available on the bus after bootup („outgoing
event“) or when being no longer accessible because of being switched off or disconnected from the bus
(„incoming event“).
5.8. Compilation and load of hardware and software configuration
After complete hardware project configuration and once having entered all parameters the project must be
compiled („translated“) and exported to the PLC.
5.9. Restore Factory Defaults
5.9.1. Factory Setup using the Engineering Tool
The engineering tool may be used to restore default values in the encoder settings. „Restore Factory
Defaults“ is accessed in the device view under context menu item „Online & diagnostics“.