BUDE_Manual-CANopen_EN.doc
29/55
Baumer Hübner GmbH
23.10.2012/bja
Berlin, Germany
Object 100A
Manufacturer software version
Subindex
0
Data type
Unsigned 32
Access
Read only
Default
EEPROM
No
Description
Software version in ASCII
Values
Data 0..3
31h 2Eh 30h 30h
= "1.00“
Objekt 100C
Guard Time
SubIndex
0
DatenTyp
Unsigned 16
Zugriff
ReadWrite
Default
0h
EEPROM
Yes
Beschreibung
Timer für Nodeguarding in ms
Werte
0 - 65535
Objekt 100D
Life Time Factor
SubIndex
0
DatenTyp
Unsigned 8
Zugriff
ReadWrite
Default
0h
EEPROM
Yes
Beschreibung
Life Time Factor x Guard Time = Life time
Werte
0 - 255