There are 3 stages of charging the Ba�ery .
①
②
This is for professional installers, you can keep it
if you do not know.
Shutdown 20%:
The inverter will shutdown if the SOC
below this value.
Low Ba� 35%:
The inverter will alarm if the SOC
below this value.
Restart 50%:
Ba�ery SOC at 50% AC output will resume.
③
Float V
53.6V
20%
35%
50%
-5
Absorption V
57.6V
Equalization V
57.6V
Equalization Days
Shutdown
Low Batt
Restart
TEMPCO(mV/C/Cell)
Batt Resistance
30 days
Equalization Hours
3.0
hours
25mOhms
Battery Setting
Set3
Batt
①
②
③
Recommended ba�ery se�ngs
Battery Type
AGM (or PCC)
Absorption Stage
14.2v (57.6v)
13.4v (53.6v)
Float Stage
Torque value
(every 30 days 3hr )
14.2v(57.6v)
Gel
14.1v (56.4v)
13.5v (54.0v)
Wet
14.7v (59.0v)
13.7v (55.0v)
14.7v(59.0v)
Lithium
Follow its BMS voltage parameters
Batterie- Typ
Absorptionsphase
Schwebestufe
Wert des Drehmoments
(alle 30 Tage 3 Stunden)
AGM (or PCC)
14.2v (57.6v)
13.4v (53.6v)
14.2v (57.6v)
Gel
14.1v (56.4v)
13.5v (54.0v)
Nass
14.7v (59.0v)
13.7v (55.0v)
14.7v (59.0v)
Lithium
BMS-Spannungsparameter beachten
Es gibt 3 Stufen des Aufladens der Batterie.
Dies ist für professionelle Installateure, Sie können es
behalten wenn Sie es nicht wissen.
Abschaltung 20%:
Der Wechselrichter schaltet sich
ab, wenn der SOC unter diesem Wert liegt.
Niedriger Batteriestand 35%:
Der Wechselrichter
schlägt Alarm, wenn der SOC-Wert unter diesen Wert
fällt.
Wiederanlauf 50%:
Batterie-SOC bei 50% AC-Ausgang
wird wieder aufgenommen.
KW
- 31-
5.6 Ba�ery Setup Menu
Grid Signal:
Disable.
Grid Charge
Gen Charge
Grid Signal
Gen Signal
Gen Max Run Time
0.0 hours
Gen Down Time
0.5 hours
Battery Setting
Start
A
30%
30%
40A
40A
Batt
Set2
①
②
③
This is Ba�ery Setup page.
Start =30%:
Percent S.O.C at 30% system will AutoStart a
connected generator to charge the ba�ery bank.
A = 40A:
Charge rate of 40A from the a�ached
generator in Amps.
Gen Charge:
uses the gen input of the system to charge
ba�ery bank from an a�ached generator.
Gen Signal:
Normally open relay that closes when the
Gen Start signal state is ac�ve.
Gen Max Run Time:
It indicates the longest �me
Generator can run in one day, when �me is up, the
Generator will be turned off. 24H means that it does
not shut down all the �me.
Gen Down Time:
It indicates the delay �me of the
Generator to shut down a�er it has reached the running
�me.
①③
Start =30%:
No use
,
Just for customiza�on.
A = 40A:
It indicates the Current that the
Grid charges the Ba�ery.
Grid Charge:
It indicates that the grid charges
the ba�ery.
This is Grid Charge, you need select.
②
Batt Mode
Lithium
Use Batt V
Battery Setting
Activate Battery
Max A Charge
Batt Capacity
Max A Discharge
40A
40A
400Ah
Batt
Mode
Use Batt %
No Batt
Ba�ery capacity:
it tells Deye hybrid inverter to know
your ba�ery bank size.
Use Ba� V:
Use Ba�ery Voltage for all the se�ngs (V).
Use Ba� %:
Use Ba�ery SOC for all the se�ngs (%).
Max. A charge/discharge:
Max ba�ery charge/discharge
current(0-115A for 5KW model, 0-90A for 3.6KW model).
For AGM and Flooded, we recommend Ah ba�ery
size x 20%= Charge/Discharge amps.
. For Lithium, we recommend Ah ba�ery size x 50% =
Charge/Discharge amps.
. For Gel, follow manufacturer' s instruc�ons.
No Ba�:
�ck this item if no ba�ery is connected to the system.
Ac�ve ba�ery:
This feature will help recover a ba�ery that is over discharged by slowly charging from
the solar array or grid.
07/08/2021 11:11:10 Thu
76%
2.00
KW
-6.00
KW
0.00
KW
KW
0
15
0
12
0
12
0
12
ON
Signal
on
2.00
This page tells the PV and diesel generator
power the load and ba�ery.
6
KW
- 32 -
Float V
53.6V
20%
35%
50%
-5
Absorption V
57.6V
Equalization V
57.6V
Equalization Days
Shutdown
Low Batt
Restart
TEMPCO(mV/C/Cell)
Batt Resistance
30 days
Equalization Hours
3.0
hours
25mOhms
Battery Setting
Set3
Batt
①
②
③
Lithium Mode
Shutdown
Low Batt
Restart
40%
20%
10%
00
Battery Setting
Set3
Batt
Lithium Mode:
This is BMS protocol.Please reference
the document(Approved Ba�ery).
Shutdown 10%:
It indicates the inverter will shutdown
if the SOC below this value.
Low Ba� 20%:
It indicates the inverter will alarm if the
SOC below this value.
Restart 40%:
Ba�ery voltage at 40% AC output will
resume.
This page tells generator output voltage, frequency,
power. And, how much energy is used from generator.
Power: 6000W
Today=10 KWH
Total =10 KWH
Generator
V_L1: 230V
V_L2: 230V
V_L3: 230V
P_L1: 2KW
P_L2: 2KW
P_L3: 2KW
There are 3 stages of charging the Ba�ery .
①
②
This is for professional installers, you can keep it
if you do not know.
Shutdown 20%
:
The inverter will shutdown if the SOC
below this value.
Low Ba� 35%:
The inverter will alarm if the SOC
below this value.
Restart 50%:
Ba�ery SOC at 50% AC output will resume.
③
Auf dieser Seite erfahren Sie, wie die PV-Anlage
und der Dieselgenerator die Last und die Batterie
versorgen.
Diese Seite gibt Auskunft über die Ausgangsspannung und
die Frequenz des Generators, Leistung: 6000W Heute=10
KWH Leistung. Und, wie viel Energie vom Generator ver-
braucht wird.