MNL-126509
April 4, 2013
Page 115
In the above tables, all values are based on 1996 NEC articles 430 and 310 (NFPA 70). These values are
provided as a general guide; however, the information given on the motor nameplate supersedes the
above information.
8.2.7
Pneumatic Leaks
Each unit is tested prior to leaving the manufacturing facility. All loose or leaking fittings are tightened
prior to shipping. During the shipping process pneumatic connections may work loose and leaks may
develop. Ensure each unit is leak tested prior to being placed in full operational usage.
3 PHASE
Motor
Hp
Full Load Amps
Fuse Amps
a
a.
Dual element time delay fuse Amps.
Minimum Wire Size
b
b.
Normal Copper wire with THW, THWN or XHHW insulation.
208 V
230 V
460V
208 V
230 V
460V
208 V
230 V
460V
2
7.5
6.8
3.4
12
10
5.6
14
14
14
3
10.6
9.6
4.8
17.5
15
8
14
14
14
5
16.7
15.2
7.6
25
25
12
10
12
14
7.5
24.2
22
11
40
30
17.5
8
10
14
10
30.8
28
14
50
40
20
8
8
12
15
46.2
42
21
60
60
30
6
6
10
20
59.4
54
27
90
80
40
4
4
8
25
74.8
68
34
100
100
50
3
4
8
30
88
80
40
125
100
60
2
3
8
40
114
104
52
175
150
80
0
1
6
50
143
130
65
200
200
100
30
20
4
60
169
154
77
250
200
100
40
30
3
75
211.2
192
96
300
300
150
300
250
1
100
273
248
124
400
350
175
500
350
20
125
343.2
312
156
500
400
200
2-40
2-30
30
150
396
360
180
600
500
250
2-300
2-40
40
^
WARNING
Never tighten or adjust fittings or connections under pressure. Always depressurize first.