Battery Tender

®

 Plus 6V1.25A: 

 

Stage 1) Bulk Charge:

  Red Light On, Green Light Off, Constant Current = 1.25 Amps, 

Transition to Stage 2, Absorption Charge when battery voltage reaches 7.25 VDC. 

Stage 2) Absorption Charge: 

Red Light On, Absorption Voltage = 7.25 VDC Transition 

to Float Charge when battery charging current drops below 0.1 amp or until 6 to 8 hours 
have elapses. 
Stage 3) There is no Equalization Charge, Go directly to stage 4. 

Stage 4) Float Charge:

  Red Light Off, Green Light On.  Float Voltage = 6.6 VDC.  If 

an external load is applied to the battery while the charger is in stage 4, Float Charge, and 
if the battery voltage drops below a range between 6.0 to 6.25 VDC, then the charge 
cycle restarts. 
 
 

Approximately

80% Recharged

Charging Time (Hours)

Absorption

(6 to 8 Hours Max)

Battery Tender     Plus Battery Charger

6 Vdc 1.25 Adc Output

Typical Charging Curve

7.25 Volts

  8.0

Bulk Charge

  5.0

  5.5

0

1

2

  6.0

  6.5

  7.0

  7.5

5

3

4

6

7

1.25 Amps

  9.0

  8.5

  9.5

10.0

Battery

Terminal

Voltage

(VOLTS)

R

1.2

0.1 Amp

13

Float / Maintenance

6.6 Volts

8

9

10

11

12

16

14

15

0.1

0.2

0

0.6

0.4

1.0

0.8

100% 

Recharged

2.0

1.6

1.25

1.4

1.8

Battery

Charging

Current

(AMPS)

 

Figure 1

  Charging Graph:  Battery Tender

®

 Plus 6V1.25A 

 
 
 
 
 