4. Trouble Shooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No  indication  and  alarm  in  the  front 

display panel even though the mains is 

normal.   

The  AC  input  power  is  not 

connected well. 

Check  if  input  cable  firmly 

connected to the mains.   

The warning code 0B. 

EPO  function  is  activated.  At 

this time, the EPO switch is in 

“OFF”  status  or  the  jumper  is 

open. 

Set  the  circuit  in  closed 

position  to  disable  the  EPO 

function.   

The warning code 01. 

The  external  or  internal 

battery 

is 

incorrectly 

connected. 

Check  if  all  batteries  are 

connected well. 

The warning code 09. 

UPS is overload.   

Remove excess loads from UPS 

output. 

UPS  is  overloaded.  Devices 

connected  to  the UPS  are  fed 

directly  by  the  electrical 
network via the Bypass. 

Remove excess loads from UPS 

output. 

After  repetitive  overloads,  the 

UPS  is  locked  in  the  Bypass 

mode.  Connected  devices  are 

fed directly by the mains. 

Remove excess loads from UPS 

output  first.  Then  shut  down 

the UPS and restart it. 

Fault code is shown as 43.   

UPS  is  overload  too  long  and 

becomes fault. Then UPS shut 

down automatically. 

Remove excess loads from UPS 

output and restart it. 

Fault code is shown as 14,

 

15,

 

16,

 

17,

 

18 or 19,   

The 

UPS 

shut 

down 

automatically  because  short 

circuit  occurs  on  the  UPS 

output. 

Check  output  wiring  and  if 

connected devices are in short 

circuit status. 

Other  fault  codes  are  shown  on  LCD 

display and alarm beeps continuously. 

A  UPS  internal  fault  has 

occurred.   

Contact your dealer 

Battery  backup  time  is  shorter  than 

nominal value. 

Batteries are not fully charged. 

Charge  the  batteries  for  at 

least  7  hours  and  then  check 

capacity.  If  the  problem  still 

persists, consult your dealer.   

Batteries defect 

Contact your dealer to replace 

the battery. 

The warning code 0A. 

Fan  is  locked  or  not  working. 

Or the UPS temperature is too 

high. 

Check fans and notify dealer.   

The warning code 02. 

The  input  neutral  wire  is 

disconnected. 

Check  and  correct  the  input 

neutral  connection.  If  the 

connection  is  ok  and  the 

warning  is  still  displaying, 

please refer to the LCD setting 

section,  to  enter  the  neutral 
loss check menu, to see if the 

parameter3  is  “CHE”.  If  it  is, 

please  press  the  “Enter”  key 

firstly to make the “CHE” flash 

and  press  the  “Enter”  key 

secondly to make the UPS clear 

the  alarm.  If  the  warning  still 

exists, please check input fuses 

of L2 and L3. 

The  L2  or  L3  input  fuse  is 

broken. 

Replace the fuse. 

Summary of Contents for 15K DUAL

Page 1: ...3 3 208V 15K L 20K L DUAL Online UPS Uninterruptible Power Supply System Version 1 0 User Manual...

Page 2: ...responsibility or liability for loss or damages whether direct indirect consequential or incidental which might arise out of the use of such information The use of any such information will be entirel...

Page 3: ...ND INSPECTION 4 2 2 WIRING TERMINAL VIEW 5 2 3 SINGLE UPS INSTALLATION 6 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 7 2 5 SOFTWARE INSTALLATION 8 3 OPERATION 9 3 1 INITIAL OPERATION 9 3 2 SCREEN DESCRIP...

Page 4: ...on the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output terminal Place cables in such a way that no one can...

Page 5: ...lert the electrical maintenance personnel of the presence of a UPS in the circuit The label will bear the following or an equivalent text The power input for this unit must be three phase rated in acc...

Page 6: ...us experience 1 6 Standards Safety UL 1778 CSA C22 2 No 107 3 14 EMI Conducted Emission FCC Part 15 Subpart B Class A Radiated Emission FCC Part 15 Subpart B Class A NOTE This equipment has been teste...

Page 7: ...RS 232 cable option One USB cable One parallel cable only available for parallel model One shared current cable only available for parallel model NOTE Before the installation please inspect the unit B...

Page 8: ...cation port only for firmware updates 2 USB communication port 3 Emergency power off function connector EPO connector 4 Share current port only available for parallel model 5 Parallel port only availa...

Page 9: ...imum input current The receptacle may be damaged and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all the connected devices before connecting to the UPS 4 Pre...

Page 10: ...n a chain make sure you modify the UPS setting accordingly Connection with wrong battery voltage may cause irreversible damage of the UPS Pay special attention to the polarity marking on external batt...

Page 11: ...8 Wiring diagram of parallel system 2 5 Software Installation For optimal computer system protection install UPS monitoring software to configure UPS shutdown operation...

Page 12: ...enter to No Output mode 3 2 LED Indicators and LCD Panel LCD LED Indicators There are 4 LEDs on front panel to show the UPS working status Mode LED Bypass Line Battery Fault UPS On Standby mode Bypas...

Page 13: ...ALL INFO VOL CALI CURR CALI INITIAL ELECTRICAL BATTERY MISCELLANEOUS UPS SELFTEST ELECTRICAL BATTERY MISCELLANEOUS PASSWORD 0000 PARAMETER INFO RATED INFO BASIC INFO Menu tree 3 3 1 Main screen Upon p...

Page 14: ...2018 11 07 ON OFF UPS BATT TEST MUTE ALL ON OFF CHARGER Touch icon to return back to main screen no matter it s in any screen of any submenu HOME CONTROL ON OFF UPS MUTE ALL Confirm YES Turn ON OFF U...

Page 15: ...he screen Touch Back to return to main screen immediately or No to cancel this operation and back to main screen It will show Cancel battery test if the UPS is in test DATALOG INFO SETTING MEASURE CON...

Page 16: ...O DATALOG INFO SETTING MEASURE CONTROL HOME 20KVA Bypass Mode 19 52 36 2018 11 07 ON OFF UPS BATT TEST MUTE ALL ON OFF CHARGER Turn Off Charger YES NO TURN ON CHARGER TURN OFF CHARGER 3 3 3 Measure sc...

Page 17: ...ion Temperature Temperature of L1 L2 and L3 phases DATALOG INFO SETTING MEASURE CONTROL HOME 20KVA Bypass Mode 19 52 36 2018 11 07 INPUT W INPUT VA INPUT CURR INPUT PF L1 L2 L3 TOTAL W 4W 4W 4W 0 0 0...

Page 18: ...r Maintainer GENERAL Date Time Y Y Y Y Y Y Y Y Y Language Y Y Y Y Y Y Y Y Y Input Source Y Y Y Contact Y Y Y Y Y Y Y Y Y Phone Y Y Y Y Y Y Y Y Y Mail Y Y Y Y Y Y Y Y Y Audible Alarm Y Y Y Y Y Y Y Y Y...

Page 19: ...ALOG INFO SETTING MEASURE CONTROL HOME 20KVA Bypass Mode 19 52 36 2018 11 07 GENERAL ADVANCE Date Time Language Input Source Contact Phone Mail English Line 0 0 0 2018 11 08 15 47 30 General screen pa...

Page 20: ...l Mute When enable is selected all the faults and warnings will be mute It will show icon on the top right corner of the main screen Mode Mute UPS status mode alarm enable disable If Mode Mute is acti...

Page 21: ...F Mode Bypass Forbid 120V 60Hz Disable Disable Electrical Setting Page 1 Output Voltage Select the output rated voltage There are two options 120V and 127V 120Vac is default setting Output Frequency S...

Page 22: ...bypass when manually turning off the UPS Bypass Voltage Range Set the bypass voltage range L Low voltage point for bypass The setting range is 96V 110V 96V is default setting H High voltage point for...

Page 23: ...s 10 0V 12 0V 10 7V is default setting The setting is only available for long run model Battery Parameter Battery AH setting battery capacity 9Ah is default setting MISCELLANEOUS DATALOG INFO SETTING...

Page 24: ...Setting menu page it s required to enter password Please contact your local dealer to get maintainer password CAUTION This setting menu is only for qualified technician Otherwise mis operation will c...

Page 25: ...2018 11 07 SYS PARAMETER INSTALL INFO VOL CALI CURR CALI LV Charger Number INITIAL UPS Type 3PCS SYS PARAMETER Page 2 Charger Number The number of charging boards installed on the UPS NOTE It s requi...

Page 26: ...ncrease 0 1 and press down key to decrease 0 1 Press OK key to confirm the modification DATALOG INFO SETTING MEASURE CONTROL HOME 20KVA StanbyMode 19 52 36 2018 11 07 SYS PARAMETER INSTALL INFO VOL CA...

Page 27: ...the modification Bypass VOL Bypass voltage calibration Increment of each click is 0 1 no matter it s pressing up or down key Press up key to increase 0 1 and press down key to decrease 0 1 Press OK ke...

Page 28: ...tial the Datalog YES NO INITIAL DATALOG Page DATALOG After pressing the confirmation window will pop up as shown in above screen Touch YES to clean the DATALOG page Touch Back or No to cancel this ope...

Page 29: ...ancel this operation and back to INITIAL menu page DATALOG INFO SETTING MEASURE CONTROL HOME 20KVA StanbyMode 19 52 36 2018 11 07 SYS PARAMETER INSTALL INFO VOL CALI CURR CALI DATA LOG INITIAL PARAMET...

Page 30: ...55 Hz for 50Hz system or within 55 65 Hz for 60Hz system Disable is the default setting Bypass Forbid Enable Bypass Forbid is enabled It s not allowed for running in Bypass mode under any situations D...

Page 31: ...ypass Mode 19 52 36 2018 11 07 ELECTRONIC BATTERY MISCELLANEOUS BATT Warning VOL Shutdown VOL BATT Age BATT Parameters 10 7V 14 4V BATT AH HIGH LOW 24 9 11 5V UPS SELFTEST Battery setting page Battery...

Page 32: ...S will cancel this operation UPS SELFTEST unknown R Phase PFC Test Step 0 0 INV Test Step S Phase T Phase unknown unknown unknown unknown unknown R Phase S Phase T Phase This function is only effectiv...

Page 33: ...out manufacturer Service Contact The contact name is set in Basic Setting Service Phone The listed numbers are set in Basic Setting Service Mail The service email account is set in Basic Setting DATAL...

Page 34: ...TT Warning VOL HIGH Shutdown VOL 990Min Shutdown Delay Restore Delay 10 7V 0min 0min 14 4V 11 5V 10 LOW BATT Number Parameter Information Page 2 BATT Mode Work Time The maximum discharge time in batte...

Page 35: ...Bypass mode NOTE When UPS is in Bypass mode the output voltage will be directed from mains after you switch on the input breaker In Bypass mode the load is not protected by the UPS To protect your pr...

Page 36: ...pacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery voltage drops to the alarm level the buzzer will beep once every sec to remind users that the ba...

Page 37: ...d technicians When the UPS needs to repair or service and the load could not be shut off the UPS needs to be put into maintenance mode 1 First switch off the UPS 2 Then remove the cover of maintenance...

Page 38: ...ut breaker of this unit 3 Turn off the battery breaker only available in long run model and remove the parallel and share current cables And then remove the unit from the parallel system Second method...

Page 39: ...output line to line short circuited None 66 Inverter current sample abnormal None 1A Inverter A negative power fault None 67 Bypass O P short circuited None 1B Inverter B negative power fault None 68...

Page 40: ...04 IP phase abnormal 33 Locked in bypass after overload 3 times in 30 minutes 05 Bypass phase abnormal 34 Converter current unbalanced 07 Over charge 3A Cover of maintain switch is open 08 Low batter...

Page 41: ...UPS shut down automatically Remove excess loads from UPS output and restart it Fault code is shown as 14 15 16 17 18 or 19 The UPS shut down automatically because short circuit occurs on the UPS outp...

Page 42: ...d precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the grou...

Page 43: ...94 Battery Mode 93 5 BATTERY Standard Model Type 12 V 9 Ah 12 V 9 Ah Numbers 10 10 pcs x 2 strings Recharge Time 9 hours recover to 90 capacity Charging Current max 4A 8A 12A 10 Adjustable Parallelabl...