The pickup setting determines the voltage pickup level of the element. Voltage pickup is based on PN.
The time delay setting controls how long it takes the trip output to become TRUE after the pickup output
becomes TRUE. When the monitored voltage increases above the pickup threshold, the pickup output
(47PU) becomes TRUE and the timer starts. If the voltage remains above the pickup threshold for the
duration of the time delay setting, the trip output (47T) becomes TRUE. If the voltage decreases below
the dropout ratio of 98 percent, the timer is reset to zero.
If the 60FL element trip logic is TRUE and V block is enabled for negative-sequence blocking <Q>, all
functions that use the negative-sequence voltage (V
2
) are blocked. For more information on the 60FL
function, see the paragraphs later in this section.
If the target is enabled for the 47 element, the target reporting function will record a target when the trip
output is TRUE and the fault recording function trip logic expression is TRUE. See Section 6,
Reporting
and Alarm Functions, Fault Reporting
, for more information about target reporting.
BESTlogic Settings for Negative-Sequence Overvoltage
BESTlogic settings are made from the
BESTlogic Function Element
screen in BESTCOMS. Figure 4-44
illustrates the BESTCOMS screen used to select BESTlogic settings for the negative-sequence
overvoltage function. To open the screen, select
Voltage Protection
from the
Screens
pull-down menu
and then select the
47
Tab. Then select the
BESTlogic
button at the bottom of the screen. Alternately,
settings may be made using the SL-47 ASCII command.
Figure 4-44. BESTlogic Function Element Screen, Negative Sequence (47)
At the top center of the
BESTlogic Function Element
screen is a pull-down menu labeled
Logic
. This
menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. A custom logic
scheme must be created and selected in the
Logic
pull-down menu at the top of the screen before
BESTlogic settings can be changed. See Section 7,
BESTlogic Programmable Logic
.
Enable the negative-sequence overvoltage function by selecting its mode of operation from the
Mode
pull-down menu. To connect the elements inputs, select the button for the corresponding input in the
BESTlogic Function Element
screen. The
BESTlogic Expression Builder
screen will open. Select the
expression type to be used. Then, select the BESTlogic variable, or series of variables to be connected to
the input. Select
Save
when finished to return to the
BESTlogic Function Element
screen. For more
details on the
BESTlogic Expression Builder
, see Section 7,
BESTlogic Programmable Logic
. Select
Done
when the settings have been completely edited.
9365200990 Rev F
BE1-CDS240 Protection and Control
4-49
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......