27R threshold setting, the overcurrent element will be blocked. When set for this mode of operation, the
51P pickup setting is typically set near or below load current levels.
When set for
Restraint
mode of operation, the
pickup
of the phase overcurrent element is adjusted based
upon the magnitude of the measured voltage. Figure 4-26 shows how the overcurrent pickup threshold
setting is adjusted in response to the measured voltage level. Equation 4-1 determines the pickup level
for the 51P elements when the measured voltage is between 25% and 100% of the 27R threshold setting.
Below 25%, the pickup level stays at 25%. Above 100%, the pickup level stays at 100%. For example, if
the 27R threshold is set for 120V and the measured voltage on the appropriate phase is 100V (83% of
the 27R threshold setting), the overcurrent pickup level for that phase will be reduced to 83% of its
setting. When set for this mode of operation, the 51P pickup setting is typically set above worst case, load
current levels.
Figure 4-26. 51P Pickup Level Compensation
The 51/27R function can be set to monitor either Vpp or Vpn depending upon the VTP connection
settings. See Section 3,
Input and Output Functions, Power System Inputs
, for more detail on how to set
the VTP Connections. Table 4-14 shows which voltage measurements are used by each phase
overcurrent element for each possible VTP connection and 51/27 voltage monitoring mode setting.
Table 4-14. VTP Connection Cross Reference
VTP Connection
51/27 Mode
51A
51B
51C
4W Vpp
Vab
Vbc
Vca
4W Vpn
Van
Vbn
Vcn
3W Vpp
Vab
Vbc
Vca
AN Vpn
Van
N/A
N/A
BN Vpn
N/A
Vbn
N/A
CN Vpn
N/A
N/A
Vcn
AB Vpp
Vab
N/A
N/A
BC Vpp
N/A
Vbc
N/A
CA Vpp
N/A
N/A
Vca
When single-phase voltage sensing is used, only the overcurrent element on the phase with voltage
magnitude information is affected by the 51/27R feature. Thus, in voltage control mode, the 51 elements
on the two unmonitored phases will always be disabled. In voltage restraint mode, the 51 elements on the
two unmonitored phases will not have their overcurrent pickup settings adjusted from 100%.
NOTE
For single-phase sensing, the unmonitored phase is not restrained or controlled.
These phases are marked in the table by N/A (not applicable).
9365200990 Rev F
BE1-CDS240 Protection and Control
4-31
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......