BE1-951
Reporting and Alarm Functions
6-3
RG-TIME Command
Purpose:
Report or set the clocks time setting.
Syntax:
RG-TIME[=<hr:mn:sc>] or RG-TIME[=<hr:mn<f>sc>]
Comments:
Password access privilege G or R is required to change settings. Default time setting on
power-up is 00:00:00.
RG-TIME Command Examples
1.
Read the clock’s current time setting (programmed in 12 hour format).
>RG-TIME
12:24P45
2.
Set a new time in 12 hour format.
>RG-TIME=11:24P00
GENERAL STATUS REPORTING
BE1-951 relays have extensive capabilities for reporting relay status. This is important for determining the
health and status of the system for diagnostics and troubleshooting. Throughout this manual, reference is
made to the RG-STAT (report general, status) report and the appropriate HMI screens for determining the
status of various functions.
General Status Report
A General Status report is available through the communication ports using the RG-STAT command. This
report lists all of the information required to determine the status of the relay. An example of a typical
general status report follows. In the explanation of what each line represents, cross-references are made
to the corresponding HMI screens that contain that data.
INPUT(1234) STATUS : 0000
OUTPUT(A12345) STATUS : 000000
CO-OUT(A12345) STATUS : LLLLLL
CO-43/143/243/343 STATUS : 0000
CO-101(101SC) STATUS : AFTER CLOSE(1)
CO-GROUP STATUS : L
ACTIVE LOGIC STATUS : USER
RECLOSER(79) STATUS : OFF
LOGIC VAR(00-31) STATUS : 00000000 00000000 00000000 00000000
LOGIC VAR(32-63) STATUS : 00000000 00000000 00000000 00100010
LOGIC VAR(64-95) STATUS : 01000000 00000000 00000000 00000000
ACTIVE GROUP STATUS : 0
BREAKER(52) STATUS : CLOSED
DIAG/ALARM STATUS : 0 RELAY, 0 LOGIC, 0 MAJOR, 0 MINOR
Input (1234)
This line reports the status of contact sensing inputs IN1, IN2, IN3, and IN4. Input information is available
at HMI screen 1.5.1. A 0 indicates a de-energized input and a 1 indicates an energized input. See Section
3,
Input and Output Functions for more information about contact sensing input operation.
Output (A12345)
Current output contact status is reported on this line. This information is also available at HMI screen 1.5.2.
A 0 indicates a de-energized output and a 1 indicates an energized output. More information about output
contact operation is available in Section 3,
Input and Output Functions.
CO-OUT (A12345)
This line reports the logic override of the output contacts. Logic override status is reported at HMI screen
1.5.3 and through the CO-OUT command. Section 3,
Input and Output Functions provides more information
about output logic override control.