BE1-50/51B-219/-226 General Information
9252000981 Rev G
Figure 1-4. Harmonic Rejection
Target Indicators
Gravity latched, manually reset targets indicate that current of 0.2 amperes or greater was present in the
trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See
Output Contacts
for maximum current rating.
Output Contacts
Output contacts are surge protected and rated as follows.
Resistive Ratings
120/240 Vac:
Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc:
Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc:
Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).
Type Tests
Isolation
Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric (high potential) tests as follows.
All circuits to ground:
2,828 Vdc
Input to Output Circuits:
2,000 Vac or 2,828 Vdc
Surge Withstand Capability
Qualified to IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems.
Impulse
Qualified to IEC 255-5.
Summary of Contents for BE1-50/51B-219
Page 2: ......
Page 6: ...iv BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Page 8: ...vi BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Page 10: ...ii BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Page 32: ...ii BE1 50 51B 219 226 Installation 9252000981 Rev G This page intentionally left blank...
Page 38: ...ii BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Page 46: ...5 8 BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...