9252000994 Rev N
BE1-50/51B-214/-215/-223/-225 General Information
1-1
SECTION 1
•
GENERAL INFORMATION
INTRODUCTION
BE1-50/51B-214/-215/-223/-225 protective relays are direct replacements for General Electric, IAC relays.
The BE1-50/51B-214/-215/-223 has a 5 ampere current sensing input. The BE1-50/51B-225 has a 1
ampere current sensing input. Compatible IAC model numbers are listed in Table 1-1.
Table 1-1. GE IAC Relays Suitable For Direct Replacement
IAC Model Number
Curve Type
12IAC51A
∗∗∗
A
Inverse
12IAC51B
∗∗∗
A
Inverse with Instantaneous
12IAC53A
∗∗∗
A
Very Inverse
12IAC53B
∗∗∗
A
Very Inverse with Instantaneous
12IAC55A
∗∗∗
A
Short Time
12IAC55B
∗∗∗
A
Short Time with Instantaneous
12IAC66A
∗∗
A
Long Time
12IAC66B
∗∗
A
Long Time with Instantaneous
12IAC77A
∗∗∗
A
Extremely Inverse
12IAC77B
∗∗∗
A
Extremely Inverse with Instantaneous
∗
Any digit covering all pickup ranges and 50 Hz or 60 Hz models.
To replace an existing IAC relay, perform the following steps.
1. Select the desired relay settings on your new BE1-50/51B-214/-215/-223/-225 relay.
2. Remove the existing IAC relay.
3. Attach the cover adapter to the existing case.
4. Insert the new relay.
5. Reinstall the existing connection plug.
6. Install the new Basler Electric cover.
Basler Electric BE1-50/51B-214/-215/-223/-225 protective relays are self-powered, microprocessor-
based, non-directional phase or ground relays that monitor the magnitude of a single-phase ac current to
provide accurate instantaneous and time overcurrent protection for 50 Hz or 60 Hz power systems. Each
model covers 10 popular time characteristics and a wide range of pickup settings.
FEATURES
A wide range of pickup settings and front panel selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.
Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-214/-215/-223/-225 overcurrent relays have the following standard features.
•
Independent time and instantaneous elements
•
A secure method to manually trip the breaker at the relay front panel
•
Direct reading front panel controls
•
Minimum pickup setting for safety during installation
•
Time characteristics extend to a pickup multiple of 40
•
Rugged draw-out construction with steel case
•
Gravity latching targets retain indication without power
•
Built-in accuracy eliminates internal adjustments
•
Minimum transient overreach
•
Field selectable characteristic curve selection similar to either GE IAC or ABB type curves
•
Field selectable instantaneous or integrating reset
•
Field selectable 50 or 60 Hz operation
•
Field selectable 0.0 or 0.1 second, fixed, instantaneous delay
Summary of Contents for BE1-50/51B-214
Page 2: ......
Page 6: ...iv BE1 50 51B 214 215 223 225 Introduction 9252000994 Rev N This page intentionally left blank...
Page 8: ...vi BE1 50 51B 214 215 223 225 Introduction 9252000994 Rev N This page intentionally left blank...
Page 34: ...ii BE1 50 51B 214 215 223 225 Installation 9252000994 Rev N This page intentionally left blank...
Page 42: ...ii BE1 50 51B 214 215 223 225 Testing 9252000994 Rev N This page intentionally left blank...
Page 52: ...5 10 BE1 50 51B 214 215 223 225 Testing 9252000994 Rev N This page intentionally left blank...
Page 69: ......