INSTRUCTIONS

FOR

AUTOMATIC VOLTAGE REGULATOR

AVC63-12 

AND

 AVC125-10

INTRODUCTION

The AVC63-12 and AVC125-10 Voltage
Regulators are contained in encapsulated plastic
cases.  The regulators control the amount of dc
excitation to the exciter field of conventional
brushless  synchronous generators.

Regulation is provided by sensing the generator
output voltage, converting it to a dc signal and
comparing the signal to a reference voltage signal.
An error signal is developed and used to control
the dc field power in order to maintain a constant
generator output.  

The regulator includes frequency compensation
with selectable slope, inverse-time overexcitation
shutdown, solid-state build-up circuitry, single-
phase or three-phase voltage sensing, single-
phase or three-phase shunt, or permanent magnet
generator power input, parallel droop compen-
sation, and an accessory input.  The accessory in-
put provides compatibility with accessories such as
a var/power factor controllers or excitation limiters.

ELECTRICAL SPECIFICATIONS

Power Output

AVC63-12: 12 Adc @ 63 Vdc maximum con-
tinuous.  24 Adc @ 125 Vdc forcing for 10
seconds.  Minimum field resistance: 5.25 

$

.

AVC125-10: 10 Adc @ 125 Vdc maximum
continuous.  20 Adc @ 250 Vdc forcing for 10
seconds.  Minimum field resistance, 12.5 

$

.

Input Power Requirements

Single- or three-phase, 50 to 400 Hz

AVC63-12: 90 to 153 Vac, 1092 VA
maximum continuous burden.
AVC125-10: 180 to 264 Vac, 1750 VA maxi-
mum continuous burden.

Sensing Input Voltage and Frequency

Single- or three-phase. Sensing voltage option
A:  90 to 139 Vac, sensing voltage option B:
180 to 264 Vac.  Sensing frequency option 1:
50 or 60 Hz nominal, sensing frequency option
2: 400 Hz nominal. (For more style/option
information see Table 4.)

Input Sensing Burden
Less than 1 VA.

Auxiliary Input
± 3Vdc for use with SCP250 VAR/PF Controller
or EL200 Min/Max Excitation Limiter.

External Voltage Adjust Rheostat
10k ohm, 2 W potentiometer.

Regulation Accuracy
±0.5% of voltage set point, average responding.

Voltage Drift
±0.5% voltage variation for a 40°C (104°F)
change.

Response Time
< 4 milliseconds.

Frequency Compensation
One or two V/Hz jumper selectable with knee

adjustable from 45 to 65 Hz for 50/60 Hz units
and 300 to 430 Hz for 400 Hz units.  Reference
Figure 1 for 60 Hz and Figure 2 for 400Hz
sensing models.  (Figures are not in numerical
order to conserve space in this document.)

EMI Suppression

Internal filter.  (See CE Conformity below.)

Voltage Build-Up

Provisions for automatic voltage build-up from
generator residual voltages as low as: 6 Vac for
AVC63-12 and 12 Vac for AVC125-10 units.

Overexcitation Shutdown

Overexcitation shutdown protection reduces the
output voltage to zero for the following voltages
in the times shown. Other voltages and times
are based on inverse time characteristic curves
as shown in Figures 3 and 4.

AVC63-12:
125 Vdc ±10% in approximately 10 seconds.
210 Vdc ±10% in approximately 1 second or
less.
AVC125-10:
250 Vdc ±10% in approximately 10 seconds.
370 Vdc ±10% in approximately 1 second or
less. 

Droop/Line Drop Compensation

<10 VA adjustable from 0 - 10% of rated input
current, 0.8 power factor.  (LDC compensates
for voltage drop due to line reactance and
reactive components of the load current only.)

Agency Approvals

UL Recognized per Standard 508, UL File No.
E97035.
CSA Certified per Standard CAN/CSA-C22.2
No. 14-95, CSA File No. LR 23131
CE Conformity.  Conforms to:

Radiated Emissions . . . . . . . . EN50081-2.
Radiated Immunity:
Electric field . . . . . EN61000-4-3 (10 V/m).
Conducted . . . . EN61000-4-6 (10 VRMS).
Conducted Emissions  . . . . . . EN50081-2.

(EN55011, Class A).

ESD Immunity . . . . . . . . . . . . . EN50082-2

(4 KV contact, 8 KV air).

EFT Immunity . . . . . . . . . . . . . EN50082-2

(2 KV coupling clamp).

Magnetic Immunity . . . . . . . . . EN50082-2

(30ARMS, 50 Hz).

Safety: . . . . . . . . . . . . . . . . . . EN61010-1.

Operating and Storage Temperature
-40°C to +70°C  (-40°F to +158°F).

Relative Humidity
95% non-condensing

Shock
Withstands 20 g in each of three mutually
perpendicular planes.
Vibration
Withstands the following accelerations at the

stated frequency: 4.5 g; 18 to 2000 Hz.

Weight
Approximately 1.1 kg (2.5 lbs.) 

INSTALLATION

 The regulator may be mounted in any position.
Refer to the outline drawing (Figure 5).  The
regulator may be mounted directly on the
generator set using UNF 1/4-20 or equivalent
hardware.  Select the proper hardware to
withstand any expected shipping/transportation
and operating conditions.

CONNECTIONS
Before connecting the AVC63-12 or the
AVC125-10 into your system, review the
terminal descriptions provided in Table 1, the
internal adjustments provided in Table 2, and
the  diagrams shown in Figures 6 through 8.

Table 1.  Terminal Descriptions

Term.

Number

Term.

Description

Upper Term. Strip

 CH GND

Chassis ground connection

2

Auxiliary Input from var
Power Factor Controller

3

Auxiliary Input from var
Power Factor Controller

4

Connect to 7 to use internal
voltage adjust, no
connection for external
voltage adjust

 5

1 Amp Current Transformer 

 5a

5 Amp Current Transformer 

6

Current Transformer
Common

6a

Common connection for
selectable features

7

Connect Remote Adjust
from 7 to 6a, connect to 4
for internal voltage adjust

8

Connect to 6a to select
1v/Hz underfrequency slope

9

Connect to 6a to select 3
phase sensing

Lower Term. Strip

20

Phase C sensing input

22

Phase A sensing input

24

Phase B sensing input

26

3-phase power input

28

1-phase or 3-phase power
input

30

1-phase or 3-phase power
input

F1

Field +