background image

Publication:

Rev

First Printing 

01/93

Copyright

9 2709 00 990

G

Revised

09/01

1993-2001

Basler Electric
Phone 618 654-2341
Route 143 Box 269
Highland IL 62249 USA

Power Systems Group

Fax 618 654-2351

http://www.basler.com

[email protected]

INSTRUCTIONS

FOR

VOLTAGE REGULATOR

AEC 42-7

9 2709 00 100

GENERAL INFORMATION

DESCRIPTION

The AEC 42-7 voltage regulator is designed for
use on 50/60 Hz brushless generators.  The
regulator includes frequency compensation,
overexcitation shutdown, a solid-state buildup
circuit, and EMI filtering.

ELECTRICAL SPECIFICATIONS
DC Output Power
Maximum continuous: 7 Adc at 42 Vdc
10 second Forcing:

15 Adc at 90 Vdc (at
240     Vac     supply
voltage)

Exciter Field DC Resistance
Minimum:

6 ohms

Maximum:

105 ohms

AC Power Input

Operating Range:

220 to 260 Vac

Phase:

1-Phase

Frequency:

50/60 Hz

Burden:

 <900 VA

Sensing Input:

200-252 Vac ±10%

2-phase, 50/60 Hz at
<1 VA Burden

Voltage Adjust Range:180 to 277 Vac
Regulation Accuracy: <1% No-load to Full

load, Average Sensing

Paralleling:

Input for 5 Vac from
External CT / Burden
Resistor to allow 10%
Droop

Response Time:

Less than 1.5 cycles
for ±5% change in
sensing voltage. Link
(T C) and Adjustable
Stability to optimize re-
sponse

EMI Suppression:

Internal EMI filter

Frequency Compensation Rate:

Twice volts per Hertz
(See Figure 1 for
curve)

Overexcitation Shutdown:
Time Delayed

:

Inverse 

Trip Range:

From no trip @ 50 Vdc
to instantaneous at
100. (See Figure 2.)
Disable link terminals 
(N D) provided for par-
allel operation.

Voltage Buildup

Internal provision for
automatic buildup
from 6 Vac, “SoftStart”

Power Dissipation

20 watts (typical)

PHYSICAL SPECIFICATIONS
Temperature:
Operating:

 -20°C to 60°C
(-4°F to 140°F)

Storage:

-40°C to 85°C
(-40°F to 185°F)

Vibration:

Withstands 1.3 G's at
2 to 27 Hz.;  0.036"
double amplitude at
27 to 52 Hz.; and 5
G's at 52 to 1000 Hz

Shock Withstands 

up 

to 

20

G's in each of three
mutually perpendicu-
lar axes

Weight

0.68 kg. (1.5 lbs.)

FREQUENCY COMPENSATION
The frequency compensation characteristic of
Figure 1 is used to improve system load pickup
performance by restraining voltage recovery
until frequency has also started to recover.

The regulator is shipped from the factory set at
a 47 Hz”'corner frequency” for 50 Hz systems.
For 60 Hz systems, a 57 Hz corner frequency
is achieved by removing the “50-50" external
link.

OVEREXCITATION TIME DELAY
If exciter field voltage exceeds 52 ± 2 Vdc, the
regulator automatically removes the field
current, after a time delay.  The time delay is
inversely proportional to the magnitude of the
detected field over voltage condition up to 95
±5 Vdc point.  Beyond 95 ±5 Vdc, the field
voltage is removed at a much faster rate.  This
shutdown function may be disabled for parallel
operation by linking terminals N and D
together.

INSTALLATION

MOUNTING
The regulator may be mounted on the gen-
erator in any convenient position. Refer to
outline drawing Figure 3.

 Figure 4 provides the

drilling template.

EXCITER FIELD POWER CIRCUIT

Connect reg wire to the brushless exciter
field F+ terminal, and the - wire to the field F-
terminal.  Refer to Figure 5.

If the exciter field resistance is less than 6
ohms, and if the full-load field current does not
exceed the maximum continuous current rating
of the regulator (7 Adc), a resistor of sufficient
wattage must be added in series with the field to
bring the total resistance to 6 ohms.

POWER INPUT

Connect wiring as shown in Figure 5. Power for
the regulator is derived from the generator
auxiliary winding, connected to wires 3 and 4.
The operable power input range is 220-260 Vac.

SENSING INPUTS

For sensing, wires U and V are connected to the
generator phase U and phase V respectively.
Wires X and Y are connected to the opposite
ends of the U and V phase coils, or commoned
together at the neutral (star) point.

QUADRATURE DROOP INPUT

When paralleling is required, a current
transformer (CT) and variable burden resistor
(rheostat) should be connected to terminals A
and B.  The ratio of the CT and the maximum
value of the burden must be chosen so that at
maximum current the voltage applied to
terminals A and B does not exceed 5 Vac rms.
A suitable value of burden would be a rheostat
adjustable from 0 - 5 ohms (10 Watts) for a CT
with a 1 Aac secondary current at full load.
These terminals may either be linked or left
open when paralleling is not required.

FUSES

It is recommended that a fuse or fuses with high
interruption capability be installed per the inter-
connection diagram.  A suitable fuse type would
be LittelFuse (type 3AG, rated 250 Vac, 6.3 A,
“Slo-Blo.” Dimensions are 6.3 mm x 32 mm (1
¼" x ¼").

CAUTION

The DC resistance of the exciter field must
be equal to or greater than 6 ohms and less
than 100 ohms.

NOTE

Fuse(s) MUST be installed per the
interconnection diagram to avoid
interrupting field current directly.

NOTE

The ground terminal must be bonded
either to a metal ground by the mounting
screw or by means of a cable to the most
suitable earthing point available close to
the regulator.

Reviews: