background image

8/28/20 

 

Sensor Readings 

 

The WeatherBoss comes standard with a wind speed, temperature and optical rain sensor. 

Other optional sensors include a wind direction sensor, light sensor, and humidity sensor. See more 
information below about each sensor and how the information is used. 
 

Rain Sensor 

 

The optical rain sensor is used to sense when there is rain. When the sensor detects enough run 

off, the alarm will activate. If the WeatherBoss is connected via CIS or Radio Link, it will close the 
selected vents to Step 1. The output will remain activated until the moisture level drops below the rain 
sensitivity level.

 

 

Wind Sensor/Alarm 

 

The wind sensor is used to measure wind speed and alert when the wind speed has surpassed 

the Activation Speed. There are two alarms so there can be low and high speed alarms from different 
directions.  If the optional directional sensor is attached, alarm can be activated based off the direction 
of the wind as well. The wind speed must remain above the activation speed for the length of time 
specified by the activate delay setting. The wind alarm will remain activated until the wind speed drops 
below the drop out set point wind speed (Drop Speed). The wind speed must remain below the Drop 
Speed for the length of time specified by the Drop Delay setting. The WeatherBoss will default to 
reading N (North) for wind direction if a standard anemometer is being used. 

High Activation Speed 

 

If the wind speed is greater than the High Activation Speed the alarm 

will activate. When the alarm activates, the environmental controller will close any open vents 
to the first programmed position. Choose your vent settings in the Headgrower App/Desktop or 
through CIS.  The activation set point may be programmed for any wind speed between 0 and 
99 miles per hour (0 and 159 kilometers per hour).  

Low Activation Speed - 

If the wind speed is greater than the Low Activation Speed the alarm will 

activate. When the alarm activates, the environmental controller will close any open vents to 
the first programmed position. Choose your vent settings in the Headgrower App/Desktop or 
through CIS. The activation set point may be programmed for any wind speed between 0 and 99 
miles per hour (0 and 159 kilometers per hour). 

  ***When a directional wind sensor is used, the high and low activation speeds can be used to 
set different activation points for different wind directions. For example: N, NW, W, and SW can 
all be set to activate at the High Activation Speed, while S, SE, E, and NE can all be set to activate 
at the Low Activation Speed.  

Activate Delay - 

The activate delay is the length of time that the wind speed will need to be 

above the activation set point for the alarm to activate. When the alarm activates, the 
environmental controller will close any open roof vents to the first programmed position. The 
activation delay may be programmed from 00:00 (MM:SS) to 99:99 (99 minutes:99 seconds).

 

Summary of Contents for WeatherBoss

Page 1: ...8 28 20 1 WeatherBoss Operation Manual BARTLETT Instrument Co 1032 Ave H Fort Madison IA 52627 319 372 8366 www bartinst com...

Page 2: ...MENU SCREEN 5 SETTINGS 5 CONFIGURATION 5 SENSOR READINGS 7 RAIN SENSOR 7 WEATHER SENSOR 7 TEMPERATURE SENSOR 8 HUMIDITY SENSOR OPTIONAL 8 LIGHT PHOTO SENSOR OPTIONAL 9 MANUALLY ACTIVATE ALARM 9 BLOCK...

Page 3: ...e East but a low speed for winds from the West Alarm 2 could be the opposite having a high speed alarm set for wind from the West and low speed alarm from the East This alarm could be assigned to Vent...

Page 4: ...arm is active it will change to either be yellow Force or red Alarm Light Sensor Reading Displays the current light sensor reading in micro moles per second per meter squared Wind A2 Reading Displays...

Page 5: ...the Headgrower cloud platform for remote monitoring and control of the WeatherBoss See the WiFi section for more information about firmware updates WiFi Set up Wi Fi for Firmware download and for rem...

Page 6: ...hannel for the Headgrower app See your Headgrower manual for more information Headgrower ID Displays the HEadgrower ID for your controller This is similar to your controllers serial number and cannot...

Page 7: ...rection if a standard anemometer is being used High Activation Speed If the wind speed is greater than the High Activation Speed the alarm will activate When the alarm activates the environmental cont...

Page 8: ...work provided with your humidity sensor needs to be entered into the WeatherBoss Go to Menu Configuration Humidity Cal and enter the 4 digit code provided and press Save If a humidity sensor is not be...

Page 9: ...larm The Force button may be pressed at any time to activate the output of the Weather Alarm this is a manual override feature The Weather Alarm will close any open vents to the first programmed posit...

Page 10: ...estore factory default settings The default settings are Activation Set Point 20 MPH Drop Out Set Point 15 MPH Activation Delay 4 Seconds Drop Out Delay 6 Seconds Units English Response Time 1 Wind Al...

Page 11: ...peed drops below 15 miles per hour for 6 seconds Activation Set Point 20 MPH Drop Out Set Point 15 MPH Activation Delay 4 Seconds Drop Out Delay 6 Seconds 1 Output Off Wind speed is below the activati...

Page 12: ...ays The WeatherBoss will close any open roof vents to the first programmed position when the when the wind speed exceeds 20 miles per hour The roof vents will return control of the roof vents to the e...

Page 13: ...on set point and the output has not been triggered 3 Output On Wind speed is above the activation set point output triggers immediately 4 Output On Wind speed is below the activation set point and the...

Reviews: