background image

10 

 

Menu Screen 

By pressing the Menu button – indicated by 3 bars in the top left corner -  on the Home Screen, 

you’ll be taken to the Menu Screen. The Menu Screen is a list of various options from controller info, 
WiFi settings, selecting the number of timers, and more. To navigate through the menu options, press 
and hold the green slider on the right side of the screen and slide up or down for more options. For 
more information on each component of the Menu, see the descriptions below: 

Program  

The ClimateBoss has 3 stages – DIF, DAY, and NITE. Each stage has a start time and target 

temperature. 2-zone operation will have an additional target temperature for the second zone. See the 
Programming, page 14 section for more information. 

Heat/Cool Settings 

Use to set the mode, set point, and offset for each heating and cooling output. Each heating and 

cooling output has three different modes - Auto, On, and Off. In the “Auto” mode, the controller will 
regulate the temperature to correspond with the target tempe/- the offset.  In the “On” mode 
the output is active. The controller has an On-To-Auto setting that will return the control from On mode 
to Auto mode after the programmed length of time has expired. See page 14, under Outputs, for more 
information.  In the “Off” mode the output is inactive until the setting is changed. 

The set point or target temperature is what the ideal setting for the greenhouse would be. This 

is the baseline which determines when each output comes on, based on their offset. Each output has an 
offset or step temperature to be added to (Cools) or subtracted from (Heats) the set point to determine 
when each output will activate. As the controller changes modes, the Heats and Cools will activate at 
different temperatures, based on the mode’s (DIF, DAY or NITE) set point. See the Programming, page 
14for more information. 

Vent C/D Settings   

All ClimateBoss models come equipped with at least one proportional vent output, output D. If 

you have models C or CH, you will also have an additional proportional vent output. These outputs can 
be used to control a curtain, roof vent, or vent window. Using these menu options, users will set up step 
size and 5 steps of vent percentage opening control. Settings include mode, step size, open time, 
threshold time, and 5 step vent percentages
. See Curtain/Vent Control, page 19 for more information. 

Timer/Mister 1/2 

The ClimateBoss has a two timer outputs that are not used for temperature control but can be 

used to turn on lights or other appliances at a certain time or to run mist type irrigation. The 
TIMER/Mister option has three modes of operation; TIMER, MISTER, and OFF. In the Off position, the 
timer relay will not turn on. In TIMER mode the timer relay will turn on at a designated time of day and 
run for a set length. The MISTER mode causes the timer appliance to enter an on-off cycle. In this on-off 
cycle, the timer is on for a programmed number of seconds repeating after the set number of minutes 
has expired. The timer along with the alarm output can also be used to run a shade or energy curtain. 
See page 18 for more information on programming the Time/Mister output.  

Summary of Contents for ClimateBoss

Page 1: ...CLIMATEBOSS Controller Louver Fan GHK Mode Operation Manual BARTLETT Instrument Co 1032 Avenue H Fort Madison IA 52627 319 372 8366 www bartinst com...

Page 2: ...0 Vent C D Settings 10 Timer Mister 1 2 10 Dehumidify 11 Statistics 11 Settings 11 Configuration 12 Programming 14 Stages DIF DAY NIGHT 14 Outputs Heat 1 Cool 1 14 Date Time 15 Dehumidification Vent C...

Page 3: ...ter COOL 1 to allow louvers to open In two zone mode COOL 2 and COOL 4 will not activate for 30 seconds after COOL 1 and COOL 3 respectively Definitions First we need to define and understand some ter...

Page 4: ...nly displays when Auxiliary options C or CH are enabled Press to change settings Current Stage Displays the controller s current stage DIF DAY or NITE Graph Button Press to view graph of the controlle...

Page 5: ...p to change settings Outside Weather Displays current temperature outside Tap to view status and settings of Wind Rain alarm if connected Timers Timer outputs used for lights irrigation or other equip...

Page 6: ...erature for each stage and 24hr period Helps with troubleshooting and graphical tracking Timer Mister output for lights or irrigation fogging Humidity probe input to trigger the dehumidification vent...

Page 7: ...u to lower the temperature at night to save on heating Controller Operations Target Temperature The figure below explains the workings of the stages DIF DAY and NIGHT Figure 4 shows the controller pro...

Page 8: ...to the target temperature for each output Controller Operations Output Temperature Using the information in Figure 4 Figure 5 if the time is 8 00 AM the operating stage is DIF and the target temperatu...

Page 9: ...iances but will also give a wider swing in temperature The hysteresis can be set to values of 1 2 or 3 through the menu options Using the output temperatures from Table 1 and a hysteresis setting of 1...

Page 10: ...mes on based on their offset Each output has an offset or step temperature to be added to Cools or subtracted from Heats the set point to determine when each output will activate As the controller cha...

Page 11: ...e the last reset Settings Zone 1 Low Alarm Used to set the temperature for Zone 1 low alarm Default 32 F Zone 1 High Alarm Used to set the temperature for Zone 1 high alarm Default 131 F Zone 2 Low Al...

Page 12: ...s used in conjunction with the Headgrower mobile app for remote monitoring and control of the Climate Boss See the WiFi section for more information about firmware updates WiFi Set up Wi Fi for Firmwa...

Page 13: ...parate sensor thermistor for controlling boilers or bench heat Option CH combines Option C Option H to add both a proportional Curtain Vent control and a 3rd Heat option Timer Alarm Shade The Timer an...

Page 14: ...ext screen then press save To edit a temperature follow the same steps except under the zone1 or zone2 column entering your desired temperature on the next screen You can see the timeline of your sett...

Page 15: ...btracting your step value see Table 1 on page 8 Therefore you edit this value by changing the step value seen below SP To change your offset value press the green number in the SP row Enter your value...

Page 16: ...r high You can change it to use a custom value by pressing the checkbox next to set temperature and entering a value The limits can only be set between the values of 32 and 131 Stage Enable Choose wha...

Page 17: ...are in Timed mode Press it to toggle between on and off If on the vent cycle will continue to activate at its start time every day If off the vent cycle will activate at its start time a single time b...

Page 18: ...utes format The maximum entry is 23 hours and 59 minutes 23 59 Repeat To choose whether it will repeat the following day press the repeat box like seen in Figure 10 This will toggle between on and off...

Page 19: ...rtain opens and the run time will determine how long it stays open At the end of the timer the alarm will activate sending a message to CIS that you can ignore and closing your curtain shade Curtain V...

Page 20: ...tep before the curtain vent will open or close to the next setting Tap this box to enter a value between 1 and 9 minutes Open Time You ll need to manually measure the amount of time in seconds to manu...

Page 21: ...e mid right of the screen See figure 15 The Heat 3 output is currently active if the box surrounding Heat 3 is red Grey indicates inactivity Wind Rain Alarm Integration If your operation has both our...

Page 22: ...ler s home screen The ClimateBoss also tracks the run time of each of the outputs Heat 1 Heat 2 Cool 1 Cool 2 Cool 3 Cool 4 and Heat 3 H and CH versions The ClimateBoss will store the information unti...

Page 23: ...set point see Stages page 13 during the next stage transition DIF DAY NIGHT Vent Cycle or Timer Manual Start The dehumidification vent cycle or a timer cycle can be manually started This allows you to...

Page 24: ...mum setting of 55 Minimum setting of 1 DAY target temperature 18 Maximum setting of 55 Minimum setting of 1 NITE target temperature 18 Maximum setting of 55 Minimum setting of 1 Hysteresis setting 1 N...

Page 25: ...N SETTING Temperature Speed Units Fahrenheit F mph CIS ID 1 On to Auto time 10 Heat Cool Delay 15 Hysteresis 1 cannot be changed Alarms both zones Low 32 F High 131 F Number of Zones 1 Thermistor Fail...

Page 26: ...ed when the calibration code is requested below The calibration code is also located on the label inside the humidity sensor casing To change enter your calibration code go to Menu Configuration Humid...

Reviews: