Operating Instructions 

RDW 03 Monitoring Electronics

M

The system quickly and reliably detects even small 
liquid leakages. It transmits a warning in form of an 
acoustic and optical alarm signal. At the same time, 
floating contacts take care of the transfer of corre-
sponding  messages  to  the  building  management 
and control system. 

The system is equipped with

•  Electronic monitoring system
•  Point sensor/sensor cable
•  Accessories

Applications

 Computer centers, ultraclean rooms, libraries, 
banks, insurance companies, public buildings

The contact overviews shown for the “break” and “alarm” relays under terminal assignment in the  
documentation for the connected RDW 03 are depicted with the following status: 
RDW 03 to voltage – sensor connected – operating status ready = no leakage present  
“Break” relay is energised, i.e. electrical contact between terminals 4 - 5; 
“Alarm” relays are de-energised, i.e. electrical contact between terminals 6 - 7, 9 – 10 
When the RDW 03 is disconnected from the power supply,  
the “Break” relay is de-energised = fail safe for system safety.
If a leak is detected, the “Alarm” relays are energised;  
recommendation: use terminals 6 - 7, 9 - 10 = fail safe for detecting a leak.

Technical data 

RDW 03, Type 17-85F3-8322

Enclosure

wall mounting polyester enclosure with a transp-box with  
membrane keyboard and separate terminal compartment

Dimensions (W x H x D)

166 mm x 160 mm x 84 mm

Inputs

power supply  
AC 230 V/50 Hz/5.3 VA or  DC 24 V/1.3 W ± 10 % as standard
sensor via two-wire lead  
sensor cable length: max. 1 000 m  
point sensors: max. 50 pcs 

Outputs

alarm relay, 2 separate changeover contacts  
(6 A at AC 230 V/6 A at DC 24 V) 

Memory

alarm/open circuit memory 

Method of measurement

conductive (conductive liquids > 2 µS/cm) 

Sensitivity

adjustable

Self-monitoring

sensor rupture and power failure 

Operating elements

two-step confirm button (step 1: buzzer off); on/off button

Signal

optical: LED-displays for operation/alarm/open circuit  
acoustic: piezoelectric buzzer 

Ambient temperature

0 °C to +60 °C

Protection class

IP 54

Terminal assignment