Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
3.9
Installation with enclosure type
4230-119
Attention:
The enclosure is provided for using the device in explosion protected
area of zone 22 in conformity with EN 61241-10 in a temperature
range of -20...+50 °C.
Follow the safety instructions of the manufacturer of the enclosure
and the panel heater.
The enclosure may not be operated in conditions subject to dust
accumulations ≥ 5 mm thickness in acordance with EN 61241-0 .
The enclosure must be undamaged and clean.
There must not be any foreign objects in the enclosure.
The place where the enclosure is mounted must be free of any
vibrations.
The enclosure must be fixed horizontal in both axes.
The wall where the enclosure is mounted, must be absolute planar,
otherwise the door may not close entirely tight!