Setup, Network and Communication Manual
ESTM / ESTM-L
17-88C1-*
Page 1: ...Setup Network and Communication Manual ESTM ESTM L 17 88C1...
Page 2: ......
Page 3: ...tion 7 4 3 Start Menu 8 4 4 Start and Connection 9 4 5 Parameter Functions App Menus 10 4 5 1 General Operation 10 4 6 Connected Device 12 4 7 General Overview 13 4 8 Maintenance Menu 14 4 8 1 Control...
Page 4: ...wed Page 4 35 1 Target Audience These operating instructions are intended for qualified personnel such as service technicians commissioning engineers and plc programmers All setting values must be giv...
Page 5: ...s The safety instructions given in this clause must be carefully observed DANGER When using the BARTEC TRACE COMAND make sure that the handheld device with the software installed on is suitable for th...
Page 6: ...password should be changed and only authorised persons should be supposed to know Otherwise some unauthorized persons are able to change all settings What might interrupted our processes or it can lea...
Page 7: ...ARTEC TRACE COMAND make sure that the handheld device with the software installed on is suitable for the operating environment Your local BARTEC reprehensive will help you to find a suitable device Pr...
Page 8: ...s errors or misprints shall be allowed Page 8 35 4 3 Start Menu When you start the app you will find the following options Connect device To connect to a field device see 4 4 Start and Connection Docu...
Page 9: ...bject to change without notice No claims for damage arising from alternations errors or misprints shall be allowed Page 9 35 4 4 Start and Connection Choose CONNECT DEVICE on the start screen Press SC...
Page 10: ...closed or opened see 4 8 1 Controller also MODBUS Status bit 72bit2 The device is in operation no faults indicated load is switched off See also 4 8 1 Controller Modbus Status Bit 72 2 The device is i...
Page 11: ...ht upcoming fault status Red Coloured Symbols are indicating an ALARM condition Change and Safe To save all changes always press the SAVE CHANGES button before leaving the submenu The first time after...
Page 12: ...Device name serial number With the device name the particular device can be identified easily The device name can be changed by the user The serial number is unique and can t be changed This number is...
Page 13: ...Overview In this overview the most important controller data are available on one page The bar graph shows the individual limit values and actual measured values Using the table next to it the indivi...
Page 14: ...r Adjustable pre alarm and Check status setting of the soft limiter Open sub menu see 4 8 3 Soft limiter heating power information Adjustable thresholds and condition of the Heating device Current Ope...
Page 15: ...the Heater will switch on 50 C to 500 C 58 F to 932 Control relays Hysteresis switch off heating if Process control Value above Set point Hysteresis 3K 15K Control relays Min alarm sensor 1 Adjustable...
Page 16: ...limiter Control relays and Limiter relays fault indication 999 see 4 8 5 Alarm Status Limiter Actual Value Returns measured temperature limiter Sensor Limiter Tripped Trip indication of the limiter T...
Page 17: ...t is done by the user Smart Limiter Reset The Smart Reset function automatically resets the soft limiter when the actual temperature Actual Value Soft Limiter at the sensor 2 TC2 is lower than the set...
Page 18: ...this Value and heater is switched on open failure contact alarm LED local display Modbus Input Register 70 3 faults 555 C 1031 F alarm off Pre alarm load current min If Load current is lower this Val...
Page 19: ...and Status History Tracking of previous alarms The time displayed is the time passed since the last alarm change Function Description action effects on valid values ranges alarm delay Minimum time in...
Page 20: ...of the temperature fuse that is placed at the internal hotspot Internal power circuit hotspot 135 C To prevent a high temperature breakdown in case of a malfunction temperature at load power circuit...
Page 21: ...tice Technical data subject to change without notice No claims for damage arising from alternations errors or misprints shall be allowed Page 21 35 Sensor 2 fault low short circuit Sensor limiter faul...
Page 22: ...Value is calculated or which of both sensors is active Temperature Unit Temperature unit selection If you toggle it all set values are converted to the respective unit Sensor mode Function Descriptio...
Page 23: ...e controller Process control Value see 4 8 1 Controller One sensor below The lower value of the TC1 and TC2 sensors is used for control only in availed sensor mode both sensors Process control Value s...
Page 24: ...ou activate this function it will be enabled to reset after 5 minutes this is to prevent misuse During these 5 minutes the device is blocked as described below Automatic heater check Periodically swit...
Page 25: ...ating circuit number It should be individual Max length 30 characters detailed information see following pages Modbus Address Bus address of the device 0 Modbus switched off 1 255 modbus address detai...
Page 26: ...password length 6 characters Press Change Password and enter if requested old device password and temporary Pin The device will show Changing password to And Now the New Password is saved Factory Res...
Page 27: ...DelayTime 0 hysteresis 3 minAlarm_SENSOR_1 5 minAlarm_SENSOR_2 5 minAlarm_LOAD_CURRENT 0 preAlarm_SENSOR_1min 555 preAlarm_SENSOR_2min 555 preAlarm_LOAD_CURRENTmax 0 preAlarm_DIFFERENTIAL_CURRENT 300...
Page 28: ...FROM DEVICE TO FILE The exported txt document is saved in the download folder of the mobile device The file name is the combination of the Bluetooth device name and a sequential number e g ESTM L30_1...
Page 29: ...e provided with a RS485 serial communication interface Description Data Data bit 8 bit Parity NO parity Stop bit ONE stop bit Baud rate 9600 5 3 Modbus Specifications 5 3 1 Modbus Function Code Modbus...
Page 30: ...l r w NOT USED 4 bool r w SOFT limiter reset available since firmware version 4 0 0 5 bool r w enable smart reset available since firmware version 4 0 0 When using the reset limiter function via Modbu...
Page 31: ...fault byte value 16bit 0 Limiter fault 1 Limiter tripped 2 Alarm sensor 1 above limiter set point 3 Min alarm load current OFF 0 4 Max alarm load current OFF 300 5 Max alarm leakage current OFF 300 6...
Page 32: ...AHC Operating time min 77 uint 32 Last Heater On Operating time min 100 uint 16 Soft limiter Status byte 16bit available since firmware version 4 0 0 0 Soft Limiter Status 0 OFF 1 ON 1 Heater on load...
Page 33: ...int 32 Operating time 1 175 uint 32 Operating time 2 177 uint 32 Operating time 3 179 uint 32 Operating time 4 181 uint 16 Status 0 See below 182 uint 16 Status 1 183 uint 16 Status 2 184 uint 16 Stat...
Page 34: ...e NO 21 int 16 r w Max alarm leakage current value YES 24 uint 16 r w AHC cycle time value min 25 uint 16 r w AHC min load current value YES 26 int 16 r w alarm delay NO 32 int 16 r w Hysteresis value...
Page 35: ...BARTEC GmbH Max Eyth Str 16 97980 Bad Mergentheim Deutschland Tel 49 7931 597 0 info bartec com bartec com...