Connections
APEX / SILAS
Pressurized Cabinet
Page 26 of 40
01-3704_7D0001_Manual_APC-SPC_20200617_jrs_en.docx
Rev.-
Purging gas connection
IF THE PURGING GAS SUPPLY IS DIMENSIONED INADEQUATELY,
FAULTS IN THE PURGING PHASE ARE TO BE EXPECTED.
Adjust the internal diameter of the purging gas supply to
the purging flow required.
Depending on protected volume, a pressure reducer of the size G ¼“ or G ½“ is
connected to the APEX (SILAS) pressurized cabinet. The supplied purging gas is
to be connected to it. The remaining connections are preinstalled.
The supply line must have a sufficiently large diameter to provide the requisite
volume of purging gas for purging.
Ex p volume
Connection size Pressure Supply line
< 50 litres
G ¼“
2 bar
8 mm
50 to 300 litres
G ¼“
2 bar
8 mm
300 to 700 litres
G ½“
2 bar
12 mm
700 to 1,000 litres
G ½“
3 bar
16 mm
> 1,000 litres to 1,500 litres
*
G ½“
3 bar
25 mm
*) for Ex p volumes > 1,500 litres, inlet and outlet purging gas are to be dimensioned according to the
application.
Purging gas discharge with the gas / dust version
DANGER
FAILURE TO DISCHARGE PURGING GAS INTO A SAFE ZONE IN THE CASE OF
GAS / DUST APPLICATIONS
Danger of explosion from whirled up dust!
Discharge of the purging gas into a safe zone.
At the pressure switch outlet there is an M 36 female thread which serves to
connect a pipe system for the discharge of the purge gas into a safe zone.
This is connected to APEX pressurized cabinet, type 07-3704-1***/*** or SILAS
pressurized cabinet of type, A7-3704-1***/****.