1. General information 

1.1 Information on the operating manual 

This  operating  manual  contains  important  information  on 
proper  usage  of  the  device.  Read  this  operating  manual 
carefully  before  installing  and  starting  up  the  pressure 
measuring device. 

Adhere to the safety notes and operating instructions which 
are  given  in  the  operating  manual.  Additionally  applicable 
regulations regarding occupational safety, accident  preven-
tion as well as national installation standards and engineer-
ing rules must be complied with! 

This  operating  manual  is  part  of  the  device,  must  be  kept 
nearest its location, always accessible to all employees. 

This  operating  manual  is  copyrighted.  The  contents  of  this 
operating manual reflect the version available at the time of 
printing.  It  has  been  issued  to  our  best  knowledge.  
Barksdale is not liable for any incorrect statements and their 
effects. 

– Technical modifications reserved – 

1.2 Symbols used 

 

DANGER!  –  dangerous  situation,  which  may  result  in 
death or serious injuries 

 

WARNING!  –  potentially  dangerous  situation,  which 
may result in death or serious injuries 

 

CAUTION!  –  potentially  dangerous  situation,  which 
may result in minor injuries 

!

 

CAUTION!  –  potentially  dangerous  situation,  which 
may result in physical damage  

 

NOTE  –  tips  and  information  to  ensure  a  failure-free 
operation 
 

1.3 Target group

 

 

WARNING! To avoid operator hazards and damages of 
the device, the following instructions have to be worked 
out by qualified technical personnel. 
 

1.4 Limitation of liability 

By non-observance of the operating manual, inappro-
priate use, modification or damage, no liability is as-
sumed and warranty claims will be excluded.

 

 

1.5 Intended use 

-  The probes have been developed for continuous level 

measurement. It is the operator's responsibility to check 
and verify the suitability of the device for the intended 
application. If any doubts remain, please contact our 
sales department in order to ensure proper usage. 
Barksdale is not liable for any incorrect selections and 
their effects! 

-  Permissible media are gases or liquids (no solids and 

frozen media), specified in the data sheet. In addition it 
has to be ensured, that this medium is compatible with 
the media wetted parts.  

-  The technical data listed in the current data sheet are 

engaging and must be complied with. If the data sheet 
is not available, please order or download it from our 
homepage. (http://www.barksdale.de) 

 

WARNING! – Danger through improper usage!  

1.6 Package contents 

Please verify that all listed parts are undamaged included in 
the delivery and check for consistency specified in your 
order: 

-  probe 
-  mounting instructions 

2. Product identification 

The device can be identified by its manufacturing label. It 
provides the most important data. By the ordering code the 
product can be clearly identified.

 

 

The manufacturing label must not be removed from the 
device! 

3. Mechanical installation 

3.1 Mounting and safety instructions 

 

WARNING!

 

Install the device only when depressurized 

and currentless! 

 

WARNING!

 

This device may only be installed by 

qualified technical personnel who has read and under-
stood the operating manual! 

!

 

Handle this high-sensitive electronic precision 
measuring device with care, both in packed and 
unpacked condition! 

!

 

There are no modifications/changes to be made on the 
device.  

!

 

Do not throw the package/device! 

!

 

To avoid damaging the diaphragm, remove packaging 
and protective cap directly before starting assembly. 
The delivered protective cap has to be stored! 

!

 

Place  the  protective  cap  on  the  pressure  port  again 
immediately after disassembling. 

 

Handle the unprotected diaphragm very carefully - it is 
very sensitive and may be easily damaged. 

 

Do  not  use  any  force  when  installing  the  device  to 
prevent damage of the device and the plant! 

 

When placing the device into operation or after mainte-
nance work, the probe has to be submerged slowly into 
the  medium!  A  rough  immersion  into  the  medium  can 
damage or destroy the diaphragm. 

 

If  there  is  any  danger  of  damage  by  lightning  or 
overpressure  when the device is installed outdoor,  we 
suggest 

putting 

sufficiently 

dimensioned 

overpressure  protection  between  the  supply  or  switch 
cabinet and the device 

3.2 Installation steps for probe 

-  Carefully  remove  the  pressure  measuring  device  from 

the package and dispose of the package properly. 

-  Mount the device according to your demands. 

 

Usually,  the  probe  has  been  delivered  without  mount-
ing  accessories.  For  different  mounting  demands, 
Barksdale offers as accessories mounting clamps, ter-
minal clamps and mounting flanges. 

 

Do not use freely suspended probes with an FEP cable 
if effects due to highly charging processes are ex-
pected. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

3.3 Removing the protection cap (if existing) 

For  the  protection  of  the  diaphragm,  some  of  the  probes 
have  a  plugged-on  protection  cap.  If  the  device  shall  be 
used  in  high-viscosity  media  such  as  sludge,  a  removal  of 
the  cap  before  start-up  is  necessary.  Thus,  the  sensor 
becomes  flush  and  the  medium  will  attain  quickly  to  the 
diaphragm. 

 

If  it  is  necessary  for  your  application  to  remove  the 
protection  cap,  this  has  to  be  done  with  utmost  care. 
To  prevent  a  damage  of  the  diaphragm,  please  follow 
these instructions. 

Removal by hand 

-  Hold the probe in a way that the protection cap points 

upwards. 

-  Hold  the  probe  with  one  hand  on  the  sensor  section 

(1). 

-  Remove the protection cap (2) with the other hand. 

Removal with a tool (recommended) 

-  Hold the probe in a way that the protection cap points 

upwards. 

-  Slide  a  small  tool  such  as  a  screwdriver  (8)  straight 

through  two  opposite  drill  holes  in  the  protective 
cap (2). 

-  Lever it off by moving up the handle of the screwdriver. 

 

Make sure that the sensor (7) under the protection cap 
will not be damaged! 

 

The probe must be installed in such a way that rubbing 
or  impact  of  the  device,  e.  g.  against  a  tank  wall,  is 
prevented. It is also important to consider the operating 
conditions such as flow conditions. 

4. Electrical Installation 

 

WARNING! Install the device only when currentless! 

Establish the electrical connection of the device according to 
the  technical  data  shown  on  the  manufacturing  label,  the 
following table and the wiring diagram. 

Pin configuration: 

Electrical connections 

cable colours 

Supply 

 

Supply 

 

Signal 

 (only 3-wire) 

wh (white) 

bn (brown) 

gn (green) 

Shield 

gn/ye (green / yellow) 

 
Wiring diagrams: 

2-wire-system (current) 

 

3-wire-system (current/supply) 

!

 

A  minimum  static  bending  radius  has  to  be  complied 
with. For static installation use the 10-fold cable diame-
ter, for dynamic applications use the 20-fold diameter. 

!

 

Prevent  the  damage  or  removal  of  the  PTFE  filter 
which  is  fixed  over  the  end  of  the  air  tube  on  devices 
with cable outlet and integrated air tube.  

 

Gauge  /  relative  devices  are  equipped  with  cable  with 
integrated air tube for atmospheric pressure reference. 
Install  cable  end  in  a  control  cabinet  or  suitable 
terminal  box  in  dry  area  which  is  free  of  aggressive 
gasses to avoid damages. 

 

For  the  electrical  connection  a  shielded  and  twisted 
multicore cable is recommended. 

 

 

Fig. 2 removal of protection cap 

 

 

V

S

 

A

 

/

 

V

I/U 

supply –

 

 

supply – 

V

S

 

A

p/T 

BLP2

 