TECHNICAL PRODUCT INFORMATION
Barel reserves the right to change technical specifications without further notice
6
Technical datasheet HFX and HFXE_LED_26
4.3 Battery
Batteries are to be assessed with final certification of luminaire. Charge and discharge characteristics
are suitable for use with high-temp NiCd cells, 4,8V 4Ah (4C).
4.4 Operation HFXE
Setting of 1.5h and 3h operation is selected by connection of Charging Indicator (LED) to terminals 5,
6 and 7 as described in table below.
For manual operation (no selftest) a single colour (green) LED is used. The indicator LED will be
green as long as the battery is in correct charge mode.
For a Selftest operation a bidirectional LED is used (RED / GREEN) connected such that OK =
GREEN. For connection of the bicoulor LED the green coloured LED is refered to as Anode and
Cathode
TEST:
NOTE: A full test should not be activated when the battery is empty or low capacity - this could result in a
wrong error-message.
Manual test:
By disconnecting the mains when the battery has been charged for a minimum of 24 hours.
Status of the test must be observed manually. In case of failure: repair the problem and re-test, or reset
unit by disconnecting mains.
Self-test:
By using a bipolar LED connected to the 2 of the 3 pins 5, 6 or 7 as shown above, then a self-test will be
performed. This test will automatically run a short test after 24h, then monthly and a full annual test operating
the Emergency Lamp (LAMP 1) from the battery. The test-timer includes a random-period to avoid all
luminaires to self-test at the same time. Disconnection/reset of mains and battery at the same time will reset the
test-timer. Test-program is conducted acc to IEC 62034.