TECHNICAL PRODUCT INFORMATION   

 

 

 

 

 

 

   

 

 

Barel reserves the right to change technical specifications without further notice 

 

 

 

 

Technical datasheet HFX and HFXE T8_10 

4.2  Electrical connection 

 
Electrical connections of the ballast must be done whith mains power supply off, and disconnected.  The mains supply must be  disconnected by an external 2-pole switch 
(both phases must be off). Connect “GND” to Protective Earth and chassis of the luminary or to a separate ground connection. The aluminium chassis is internally connected to 
the gnd pin. DC input: Connect – to “N” and + to “L/L1/L4”.  HFXE: Connect L1 via switch to allow battery charging while light is switched off. Indicator LED to be 
connected to 5-6 or 5-7 as indicated: 

          

       

                                 

 

4.3  Battery 

 

Batteries are to be assessed with final certification of luminaire. Charge and discharge characteristics are suitable for use with high-temp NiCd cells, 4,8V 
4Ah (4C) or 8,4V 4Ah. HFXE detects the type of battery connected, and appropriate charge/discharge and cut off values are set internally. Connect battery to 
correct polarity of HFXE “13” and “14”.

 

 
 
 
 

Summary of Contents for HFX 18

Page 1: ...INED ELECTRONIC BALLAST AND EMERGENCY INVERTER FOR EX ENVIRONMENT Author Barel AS Rev 10 Date 03 11 2014 Barel AS 9917 Kirkenes Norway www barel no CONTENTS 1 APPLICATIONS 2 2 APPROVALS 2 3 TECHNICAL...

Page 2: ...table for use in explosive gas athmospheres like Oil Industry Off On shore Installations Gas Stations Fuel Reservoirs Oil Tankers Mining Industry Mines Plants Mills Chemical Industry Production Plants...

Page 3: ...l reserves the right to change technical specifications without further notice 3 Technical datasheet HFX and HFXE T8_10 3 Technical data 3 1 Product range Power factor measured 230V 50Hz Ik max 1500A...

Page 4: ...ATION Barel reserves the right to change technical specifications without further notice 4 Technical datasheet HFX and HFXE T8_10 3 2 Mechanical data Aluminum housing fastened with 2 screws in the pla...

Page 5: ...95 C Operating temperature of the plastic material in the terminals is 30 C to 105 C Charging current 220mA 80mA permanent With one fault condition of the charging system the charging power is limite...

Page 6: ...or to a separate ground connection The aluminium chassis is internally connected to the gnd pin DC input Connect to N and to L L1 L4 HFXE Connect L1 via switch to allow battery charging while light i...

Page 7: ...hours Status of the test must be observed manually Self test By using a Bipolar LED connected to the 2 of the 3 pins 5 6 or 7 as shown above then a self test will be performed This test will automatic...

Page 8: ...oltage is in the voltage range of the ballast Check that the screws at the connection terminal are tightened Check that correct lightsources are connected and that these are ok The lamp s lights up bu...

Reviews: