background image

   

TECHNICAL PRODUCT INFORMATION

   

 

 

Barel reserves the right to change technical specifications without further notice 

 

 

 

 

Technical datasheet HFX and HFXE T8_10 

 

Applications 

 

The HFX and HFXE T8 is a series of combined electronic ballasts and 
emergency light inverter for T8 fluorescent lamps used in Ex-environments, 
suitable for installation in Ex e enclosures.

 

 
The HFX and HFXE will be suitable for use in explosive gas athmospheres like: 
 
- Oil Industry  

  

Off- & On-shore Installations, Gas Stations, Fuel  

 

 

 

 

Reservoirs, Oil Tankers 

- Mining Industry   

Mines, Plants, Mills 

- Chemical Industry  

Production Plants

 

 
 
 
 

Approvals  

 

  

Approvals : 

-

 

QAN/QAR 

 

 

 

0470 Nemko 01ATEX452Q/    
NO/NEM/QAR08.0001/04 

-

 

Ex protection Code    

 

Ex II 2 G Ex eb mb IIC T4  

-

 

IECEx Certificate :    

 

IECEx PRE 14.0039U 

-

 

ATEX no. 

 

 

 

Presafe 14 ATEX 5355U 

-

 

BRHZ no. 

 

 

 

Pending 

Reference standards : 
-   IEC 60079-0 

 

 

 

2011 

-   IEC 60079-7 

 

 

 

2006 

-   IEC 60079-18   

 

 

2009 

 

-   EN 60079-0 

 

 

 

2012 

-   EN 60079-7 

 

 

 

2007 

-   EN 60079-18   

 

 

2009 

 
In accordance with 
-   IEC 61347-2-3   

 

 

2000+A1:2004 

-   EN55015 
-   EN61547  

 

Summary of Contents for HFX 18

Page 1: ...INED ELECTRONIC BALLAST AND EMERGENCY INVERTER FOR EX ENVIRONMENT Author Barel AS Rev 10 Date 03 11 2014 Barel AS 9917 Kirkenes Norway www barel no CONTENTS 1 APPLICATIONS 2 2 APPROVALS 2 3 TECHNICAL...

Page 2: ...table for use in explosive gas athmospheres like Oil Industry Off On shore Installations Gas Stations Fuel Reservoirs Oil Tankers Mining Industry Mines Plants Mills Chemical Industry Production Plants...

Page 3: ...l reserves the right to change technical specifications without further notice 3 Technical datasheet HFX and HFXE T8_10 3 Technical data 3 1 Product range Power factor measured 230V 50Hz Ik max 1500A...

Page 4: ...ATION Barel reserves the right to change technical specifications without further notice 4 Technical datasheet HFX and HFXE T8_10 3 2 Mechanical data Aluminum housing fastened with 2 screws in the pla...

Page 5: ...95 C Operating temperature of the plastic material in the terminals is 30 C to 105 C Charging current 220mA 80mA permanent With one fault condition of the charging system the charging power is limite...

Page 6: ...or to a separate ground connection The aluminium chassis is internally connected to the gnd pin DC input Connect to N and to L L1 L4 HFXE Connect L1 via switch to allow battery charging while light i...

Page 7: ...hours Status of the test must be observed manually Self test By using a Bipolar LED connected to the 2 of the 3 pins 5 6 or 7 as shown above then a self test will be performed This test will automatic...

Page 8: ...oltage is in the voltage range of the ballast Check that the screws at the connection terminal are tightened Check that correct lightsources are connected and that these are ok The lamp s lights up bu...

Reviews: