background image

Page 

1 of 5

The CMH-29 is a field-installable combination of low 
ambient fan cycling control and a compressor cutout 
outdoor thermostat to be used with a Bard wall-
mounted heat pump.

The CMH-29 kit consists of:
•  8406-112 Low Ambient Fan Cycling Switch
•  910-2013 Relay and Compressor Cutout 

Thermostat Assembly

•  3/8" vinyl-covered clamps
•  Required fasteners
•  7960-771 Installation Instructions

The CMH-29 kit is for use with Bard models W18HA, 
W24HA, W30HA and W36HA wall-mount heat pumps.

Compressor Cutout Thermostat

Heat pump compressor operation at outdoor 
temperatures below 0° is neither desirable nor 
advantageous in terms of efficiency. An outdoor 
thermostat can be applied to take the mechanical 
heating (compressor) offline, and send the (compressor) 
signal to energize electric heat in its place (to make 
electric heat first stage heating). This can also be 
applied to limit the quantity of available electric heat. 

Bard Manufacturing Company, Inc. 
Bryan, Ohio 43506
www.bardhvac.com

Manual: 7960-771
Supersedes: 

NEW

Date: 4-14-16

CMH-29  

Low Ambient Control and 

Compressor Cutout Thermostat Kit

For Use with W18HA, W24HA, W30HA and W36HA 

Wall-Mount Heat Pumps

INSTALLATION INSTRUCTIONS

Example:

 Heat pump with 10KW second stage heat.  

Once the outdoor thermostat has switched, 15KW 

without compressor.

INSTALLATION

1.  Disconnect all power to wall-mount unit.

2.  Remove outer and inner control panel covers.

3.  Remove right side condenser inlet grille.

4.  Remove all three front service panels.

5.  Mount 910-2013 relay assembly into unit control 

panel as shown in Figure 1 on page 3. Use phillips 
head screws included with kit to attach relay to 
control panel.

6.  Remove cover from vertical gray cable duct on 

control panel to allow wire harness from installed 
relay to route into it (see Figure 1).

NOTE:

  The unit wiring diagram (included with unit 

literature assembly and also located on inner 

control panel cover) can be used to wire this 

kit. However, the following instructions listed 

here provide the necessary connections point-

by-point.