BAR-BE-QUICK inStove BS1251 Installation And Operating Instructions Download Page 1

(revision 'a')

INSET SOLID FUEL

ROOMHEATER 

FOR INSTALLATION IN

STANDARD BRITISH or IRISH

FIREPLACES CONFORMING TO

BS1251 & BS8303

INSTALLATION AND OPERATING INSTRUCTIONS

LEAVE THIS DOCUMENT WITH THE HOUSEHOLDER!

Intermittent burning solid fuel roomheater for installation in masonry

fireplace with a single dedicated chimney. 

 Wood logs

Mineral fuel (Ancit)

Approx e iciency

 50-60% 

50-60%

Nominal Output

 2.0kW 

4.5kW

Minimum air space

around fire

 Back = 0mm, Sides + Top = 100mm

Minimum clearance to

combustible materials

 Top: 400mm

 All other faces: 250mm

Read these instructions! Use only recommended fuels! 

This document,  when completed by the installer, constitutes a 'Hearth Notice' for purposes of the England and Wales

Building Regulations 2000 . It must be left with the householder and placed where it can easily be found.

APPLIANCE SERIAL NUMBER:
INSTALLED AT LOCATION:

BY:

SIGNED:                                                                                DATE:

Who certifies that this installation is safe, has been demonstrated to the

householder, conforms with current building regulations and with these

instructions

Flue Draught measured

on commissioning:

Fuel used on

commissioning

TO FIND A QUALIFIED INSTALLER, FUEL SUPPLIER or CHIMNEY SWEEP, CONTACT:

UK: 

The Solid Fuel Association, 7 Swanwick Court, Alfreton, Derbyshire DE55 7AS Tel:0845 -601-4406 

www.solidfuel.co.uk

RoI:

 Irish Nationwide Fireplace Organisation, 162 Capel Street, Dublin 1 Tel:01-801-5959 

www.fireplace.ie