Sensor Fault
Code
Description
Recommended Solution
32
Laser Power Write Error
•
Reboot the sensor
•
If the fault persists, call Banner Customer Support
1000
Acquisition Error 3
•
Reboot the sensor
•
If the fault persists, call Banner Customer Support
1011–1017
Internal Flash Error 1–7
•
Call Banner Customer Support
30000-32000
Boot Loader Error
•
Call Banner Customer Support
6.3.2 Configuration Error Codes
The following is a list of possible error codes.
Modbus TCP:
The codes are from input register 22 (holding register 1022).
EtherNet/IP:
The codes are from word 21 in the PLC Input (ZMX Output) Assembly Instance
Error Code
Description
110
Illumination Power < 1
111
Illumination Power > 100
120
Invalid Trigger Mode
130
Trigger Period < 200 ms
131
Trigger Period > 60000 ms
140
Pitch Angle < -4500
141
Pitch Angle > 4500
150
Roll Angle < -4500
151
Roll Angle > 4500
160
Yaw Angle < -18000
161
Yaw Angle > 18000
300
Invalid Discrete Polarity
2000
Anchor Point X < -2500 mm
2001
Anchor Point X > 2500 mm
2010
Anchor Point Y < -2500 mm
2011
Anchor Point Y > 2500 mm
2020
Anchor Point Z < -2500 mm
2021
Anchor Point Z > 2500 mm
2030
Bin Length X < 50 mm
2031
Bin Length X > 5000 mm
2040
Bin Width Y < 50 mm
2041
Bin Width Y > 5000 mm
2050
Bin Height Z < 50 mm
2051
Bin Height Z > 5000 mm
2052
Invalid Bin Height
2060
Fill Level Setpoint < 0%
2061
Fill Level Setpoint > 200%
2080
Peak Height Setpoint < 0
ZMX Series 3D Time of Flight Sensor
www.bannerengineering.com - Tel: + 1 888 373 6767
45