5 Configure TEACH/SET
Self-Contained Models: By default, the sensor TEACH/SET method is Two-Point Static TEACH. To perform a TEACH/SET,
use the following procedures for your preferred method.
Opposed-Mode Models: By default, the receiver TEACH/SET method is Two-Point Static TEACH. To perform a TEACH/
SET, use the following procedures for your preferred method.
Push Button
Action
Result
Two-Point
Static TEACH
1. Present the output ON target condition.
2. Press and hold the button for longer than 2
seconds to enter TEACH mode and
configure the output ON light level.
3. Present the output OFF target condition.
4. Click the button once to configure the
output OFF light level and return to Run
mode.
Accepted
1. The amber LED indicator is off and the
green indicator LED flashes three times.
2. The green and amber LED indicators flash
six times rapidly in unison (acceptance
flash).
3. The sensor returns to Run mode with valid
thresholds.
Invalid Teach Condition
1. The green and amber indicator LEDs flash
two times in unison.
2. The green and amber LED Indicators flash
six times rapidly in unison (acceptance
flash).
3. The sensor returns to Run Mode with
coerced thresholds.
Dynamic
TEACH
1. Press and hold the Push Button for greater
than 2 seconds to start the Dynamic
TEACH process.
2. Run the target application to configure the
ON and OFF conditions.
3. Click the Push Button once to stop the
Dynamic TEACH process and return to
Run mode.
Window SET
1. Present the target condition.
2. Press and hold the button for greater than
2 seconds to configure the target condition
and return to Run mode.
Light SET
Dark SET
Opposed-Mode
Models:
Opaque Mode
IO-Link
Action
Result
Two-Point
Static TEACH
1. Present the output ON target condition.
2. Send SP1 Two Value Teach TP1 command
using IO-Link to enter TEACH mode and
learn the output ON light level.
3. Present the output OFF target condition.
4. Send the SP1 Two Value Teach TP2
command using IO-Link to configure the
output OFF light level and return to Run
mode.
Accepted
1. The amber LED indicator is off and the
green indicator LED flashes three times.
2. The green and amber LED indicators flash
six times rapidly in unison (acceptance
flash).
3. The sensor returns to Run mode with valid
thresholds.
Invalid Teach Condition
1. The green and amber indicator LEDs flash
two times in unison.
2. The green and amber LED Indicators flash
six times rapidly in unison (acceptance
flash).
3. The sensor returns to Run Mode with
coerced thresholds.
Dynamic
TEACH
1. Send SP1 Dynamic Teach Start command
using IO-Link to start the Dynamic TEACH
process.
2. Run the target application to configure the
ON and OFF conditions.
3. Send SP1 Dynamic Teach Stop command
using IO-Link to stop the Dynamic TEACH
process and return to Run mode.
WORLD-BEAM QS18 Expert with IO-Link
www.bannerengineering.com - Tel: + 1 888 373 6767
15