• When a FlexPower Node receives 10 to 30V dc, it operates like a standard 10 to 30V dc Node.
• Good applications for FlexPower devices operating from batteries include sensors that require no or very little power, including dry
contacts, RTDs, and thermocouples.
The following FlexPower options are available:
• DX81, a single battery supply module;
• DX81P6, a 6-pack of lithium batteries;
• DX81H, a single battery supply module designed specifically to power the DX99 Intrinsically Safe devices with polycarbonate hous-
ings; and
• BWA-SOLAR-001, a solar power assembly that includes the solar panel, rechargeable batteries, and solar power controller.
DX81: Single battery supply module
DX81P6: Six-pack battery supply module
BWA-SOLAR-001: Solar supply; includes
solar panel, rechargeable batteries, and
controller.
DX81H: Single battery supply module de-
signed specifically to power the DX99 In-
trinsically Safe devices with polycarbonate
housings
SureCross User Configuration Tool
The User Configuration Tool (UCT) offers an easy way to link I/O points in
your wireless network, view I/O register values graphically, and set system
communication parameters when a host system is not part of the wireless net-
work.
The UCT requires a special USB to RS-485 (model number BWA-HW-006)
converter cable to pass information between your computer and the Gateway.
Download the most recent revisions of the UCT software from Banner Engi-
neering's website:
http://www.bannerengineering.com/wireless
.
SureCross Wireless I/O Network Manual
8
www.bannerengineering.com - tel: 763-544-3164
rev. I