1. Ethernet crossover cable using the Modbus/TCP or EtherNet/IP
™
communication protocol
2. Industrial Ethernet connection
3. DX80 GatewayPro
Example Layout #3
This example system layout may also be configured using the web pages. Instead of using a GatewayPro to connect to the host system,
a Gateway and Ethernet Bridge is used to achieve the same function. In this configuration, the Gateway is Modbus Slave 1.
1. Ethernet crossover cable using the Modbus/TCP or EtherNet/IP communication protocol
2. Power connection
3. DX83 Ethernet Bridge
4. Splitter cable CSRB-M1250M125.47M125.73 using Modbus RTU
5. DX80 Gateway
Typically, the Modbus RTU connection at a GatewayPro is not used because the GatewayPro contains a master and slave device. The
Modbus RTU factory default settings for a standard Gateway are: 19200 baud; 8 data bits; No stop bits; 1 parity bit; Modbus Slave ID 1.
Accessing the Web-based Configuration Screens
The configuration Web pages are served from the DX83 Ethernet Bridge or DX80 GatewayPro device and many be accessed using any
Internet browser.
Before accessing the Web-based configuration screens, configure the browser for a direct connection to the Internet. If you are experi-
encing problems connecting, verify the browser is not set to use a proxy server. Note also that a crossover Ethernet cable is required
when connecting directly from a host computer to the DX83 Ethernet Bridge or DX80 GatewayPro.
The factory default IP address for the DX83 Ethernet Bridge or DX80 GatewayPro devices is: 192.168.0.1 To change the default IP
address, set up the host PC with an IP address different from the Ethernet Bridge or Gateway Pro IP addresses. (Refer to Banner docu-
ment 133116 for detailed instructions on setting up the host computer’s network IP address.) For example, change the PC host IP ad-
dress to: 192.168.0.2. To access the configuration screens, follow these steps.
1. Open a Web browser and log into the Ethernet Bridge or GatewayPro by typing the IP address in the browser location window: http://
192.168.0.1.
The Web home page for the Ethernet Bridge or GatewayPro displays.
SureCross Wireless I/O Network Manual