8.6.4 Set the Email and Messaging Parameters
From the
Settings
>
Notifications
screen, enter the SMTP definition, login, and password for a mail server.
Important:
Only the DXM100 and DXM150 models offer SMS/text messaging capabilities.
To send email, you must supply the SMTP Server, Server Port, and login credentials. When you are only sending SMS
messages over cellular, the SMTP Server is not required.
The default SMTP port is 25 but may need to be adjusted for Ethernet-based networks. Note that many facilities block port
25. Port 587 is another common SMTP submission port.
The SMTP password is not stored in the XML configuration file, but on the DXM. After the password is entered, click on
Send
SMTP Password
to send it to the DXM. The password is stored in non-volatile memory, so reboot the DXM to recognize the
new password.
When using a GMail server, select
Situational encryption
and
Enable SMTP authentication
. The GMail server will not
allow you to send email alerts using the cellular interface. GMail may notify you that you must allow access for less secure
apps in your email settings.
For other email servers, the parameters may vary and will require information from the provider.
Figure 48. Mail and email settings
At the bottom of the screen, define the recipient to receive emails. These recipients selected in the threshold definition for
sending alert messages.
Sending SMS alerts requires that the Cellular Radio chip be installed and configured, regardless of the
Push Interface
used.
This setting allows a user to receive SMS alerts directly on their cell phone in the case of critical component changes or
failures.
1. On the
Settings
>
Notifications
screen, add recipients for SMS alerts.
2. In this section, you may change the Name of the recipient, add a phone Number, and insert a Message for the
recipient.
3. SMS alerts will be received in the format: Message Active/Inactive or Threshold Rule Name Active/Inactive
depending on the configuration.
4. Enter the phone numbers for SMS messages.
•
4G LTE cellular: Enter phone numbers without dashes. For example, a US phone number of (234) 555-1212
would be entered as 2345551212.
•
Emnify GSM cellular: Enter phone numbers using the country code, area code, and phone number. For
example, a US phone number of (234) 555-1212 would be entered as 12345551212. These cellular modems
are not certified for use in the US.