4.13 Password Manager
Figure 44. Password Manager
Click Password Manager on the PC Interface toolbar to edit the configuration access rights. The Safety Controller stores
up to three user passwords to manage different levels of access to the configuration settings. The password for User1
provides full read/write access and the ability to set access levels for User2 and User3 (user names cannot be changed).
Basic information, such as network settings, wiring diagrams, and diagnostic information, is accessible without a password.
A configuration stored on a PC or an SC-XM2 drive is not password-protected. If desired, a password requirement for
User2 and User3 may be set to change the network settings, view the configuration, and change the configuration.
"Allowed to view the configuration" option for User2 and User3 is available when "Require password to view configuration"
for User1 is checked.
NOTE: The default passwords for devices with firmware version 1.5 and later for User1, User2, and
User3, are 1901, 1902, and 1903, respectively. The default passwords for devices with firmware version
1.4 and earlier are 0000, 1111, and 2222. It is highly recommended to change the default passwords to
new values.
4.14 Saving and Confirming a Configuration
Saving a Configuration:
1. Click Save.
2. Select Save As.
3. Navigate to the folder where you wish to save the configuration.
4. Name the file (may be the same or different from the configuration name).
5. Click Save.
Confirming a Configuration (the Controller must be powered up and connected to the PC via the SC-USB2 cable):
1. Click Write Configuration to Controller.
2. Enter the password (default password is 0000).
3. Click Continue to enter the configuration mode.
4. After the Reading Configuration from the Controller process is completed, the Confirm Configuration screen
opens. Verify that the configuration is correct.
5. Scroll to the end of the configuration and click Confirm.
6. After the Writing Configuration To Controller process is completed, click Close.