![Banner R95C Instruction Manual Download Page 1](http://html1.mh-extra.com/html/banner/r95c/r95c_instruction-manual_3759265001.webp)
B
ANNER
E
NGINEERING
C
ORP
.
March 13, 2023
R95C 8-Port 2-Channel Discrete IO-Link Hub Instruction Manual
Features
Models
Overview
The R95C-8B22-KQ hub connects two discrete Input/Output channels to each of the eight unique ports, providing access to monitoring and configuring those ports
with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/Host connection.
Configuration
Figure 1 details the logic flow for each of the eight ports, while the tables define the configuration for each pin.
For more information, see P/N 233583
R95C-8B22-KQ IO-Link Data Reference Guide
and P/N 233584
R95C-8B22-KQ IODD Files
.
Figure 1:
Logic Flow
•
Compact bimodal to IO-Link device converter that connects discrete inputs and sends the
value to the IO-Link Master
•
Outputs a discrete value as received from IO-Link Master Process Data Out
•
Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One-shot,
ON/OFF Pulse-stretcher and Totalizer
•
Measurement Metrics: Count, Events Per Minute (EPM), and Duration
•
Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any of the
eight ports, Discrete Out, or the host white wire output
•
Discrete input/output can be independently configured as NPN or PNP
•
Rugged overmolded design meets IP65, IP67, and IP68
•
Connects directly to a sensor or anywhere in-line for ease of use
•
R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link devices
into an IO-Link system
C = Converter
8B22 = 8-port,
bimodal, 2
inputs, 2 outputs
K = IO-Link
Q = M12 integral
quick disconnect
Function
Converter
Control
C
Housing
R95
K
Connector
Q
8B22
Input State
Delay Mode
• Disabled
• On/Off Delay
• On/Off/Retriggerable One-shot
• On/Off Pulse Stretcher
• Totalizer
Host
Mirroring
Enable
Host Mirroring
Process Data
Input
Measurement
Statistics
Mirroring
Enabled
Enabled
Input
Disabled
Ouput
Process Data In
Measurement Statistics
Mirroring - Discrete 1 and 2 Output
• Discrete 1 and 2 Input State (active/inactive)
Process Data
Input
Process Data Out
• Discrete 1 and 2 Output State (active/inactive)
• Count
• RPM
• Duration
• Port/Channel selected state driven to Pin 2 (F) and Pin 4 (F)
Process Data
Output
Process Data Out - Discrete 1 and 2 Output
• Process Data Out selected state driven to Pin 2 (F) and Pin 4 (F)
Host Mirroring - Discrete Host Out
• Port/Channel selected state driven to Pin 2 (M)
Discrete 1 & 2
Selection
Mirroring
Enable