Banner ES-UA-5A Manual Download Page 4

E-Stop Safety Module 

– Models ES-UA-5A and ES-VA-5A

E-Stop Switch Requirements

As shown in Figures 4, 5, and 6, the E-stop switch must provide contacts which are 

closed when the switch is in the “armed” position. Once activated, the E-stop switch must 

open its contacts and be returned to the closed-contact position only by a deliberate 

action (such as twisting, pulling, or unlocking). The switch should be a “positive-opening 

type,” as described by IEC 60947-5-1. A mechanical force applied to such a button (or 

switch) is transmitted directly to the contacts, forcing them open. This ensures that the 

switch contacts will open whenever the switch is activated.
NFPA 79 specifies the following additional Emergency Stop Actuator requirements:
•   Emergency Stop push buttons shall be located at each operator control station and at 

other operating stations where emergency shutdown shall be required.

•   Stop and Emergency Stop push buttons shall be continuously operable from all control 

and operating stations where located.

•   Actuators of Emergency Stop devices shall be colored RED. The background 

immediately around the device actuator shall be colored YELLOW. The actuator of a 

push-button-operated device shall be of the palm or mushroom-head type.

•  The Emergency Stop actuator shall be a self-latching type.
NOTE:  Some applications may have additional requirements. The user must refer to all 

relevant regulations.

When a 1-channel E-stop is used, the user must guard against failure modes that 

can result in an unsafe condition, for example the failure of the contact to a short 

circuit condition. A switch with positive opening operation should be used to reduce 

the possibility of a failure of the switch to open. A short circuit failure results in loss of 

switching function. This can occur from a short across the switch contacts, a short across 

the wires connected to the switch somewhere between the switch and the  

E-Stop Safety Module, or a short to a secondary source of power. To reduce these 

possibilities, physically separate the wires from each other and from other sources of 

power (e.g., in separate wireways or conduit).
According to the definition of European standard EN 954-1, a 1-channel E-stop should 

generally be used in applications where Safety Category 2 or less (1 or B) has been 

determined via a risk-assessment procedure.
Two-channel E-stops, with positive open switches, are designed to issue a stop 

command even in the event of a single failure of this type and provide a high level of 

safety.
If the Module is configured for 2-channel E-stop, the immediate normally open output 

contacts (13-14, 23-24, 33-34, and 43-44), will open as soon as at least one of the two 

E-stop contacts opens. Although simultaneity is not required, the E-stop contacts must 

both be open at the same time and then both be closed, to reset the output contacts. 

If not, the unit will go into a lockout condition that results in the outputs opening and 

requiring a reset after the fault has been corrected.

WARNING . . . 

1-Channel Input

If a 1-channel E-stop 

button is used, a single fault (such as a 
short across the single contact or to a 
secondary source of power) can lead to 
the complete loss of safety.
A 1-channel E-stop should be used 
only in applications where such a fault 
can be excluded, or the resulting loss 
of safety cannot result in serious injury 
or death
 (Safety Category 2, 1 or B; see 
page 3).
If a 1-channel E-stop is used, separate 
the wires from each other and from 
other sources of power, by routing 
them through separate wireways or 
conduit
 in order to increase the reliability.

WARNING . . . 

Multiple 

E-Stop Switches

Whenever two or more E-stop 

switches are connected to the same E-
Stop Safety Module, the contacts of both 
switches must be connected together in 
series. This series combination is then 
wired to the respective Safety Module input. 
Never connect the contacts of multiple 
E-stop 
switches in parallel to the E-Stop Safety 
Module inputs; this defeats the switch 
contact monitoring ability of the Safety 
Module, and creates an unsafe condition 
which could result in serious injury or 
death. 

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for ES-UA-5A

Page 1: ...FPA 79 and IEC EN 60204 1 6 amp safety output contacts Plug in terminal blocks 12 24V dc 115V ac or 12 24V dc 230V ac operation External Device Monitoring one channel EDM WARNING This Emergency Stop S...

Page 2: ...tion are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are followed U S Standards Applicable...

Page 3: ...nnels each of which is the series connection of two forced guided relay contacts that are internally monitored K1 and K2 in Figures 4 and 5 If the Module detects a failure such as a welded output rela...

Page 4: ...these possibilities physically separate the wires from each other and from other sources of power e g in separate wireways or conduit According to the definition of European standard EN 954 1 a 1 cha...

Page 5: ...multitude of machine control configurations The following guidelines are general in nature The ES UA 5A and ES VA 5A Modules have no delay function Their output relay contacts open within 25 milliseco...

Page 6: ...utput dc common V 12 24V dc Y32 Y35 Jumper For power connection see Figure 6 Reset Switch MSC2 MSC3 MSC4 E Stop Switch Figure 4 Hookup 2 Channel E Stop Applications WARNING Wiring of Arc Suppressors I...

Page 7: ...S35 Arc Suppressors see WARNING on page 6 6A max K1D K2D 43 44 6A max K1E K2E 51 52 Non safety Auxiliary Monitor Contact Y31 Y30 Non safety Monitor Outputs 20mA max each Output Outputs Energized Powe...

Page 8: ...ES VA 5A may be used also with automatic reset If no MSC monitor contacts are monitored a jumper must be installed between terminals S31 and S32 see Figures 4 and 5 The E Stop Safety Module will reset...

Page 9: ...wiring Return to step 2 after the cause of the problem has been corrected 7 Close the enclosure Apply power to the Machine Control Elements and perform the Periodic Checkout Procedure NOTE If more tha...

Page 10: ...escription of the problem If they conclude that a component is defective they will issue an RMA Return Merchandise Authorization number for your paperwork and give you the proper shipping address 2 Pa...

Page 11: ...page 6 Solid State Monitor Outputs Two non safety solid state dc outputs Output at Y32 monitors state of outputs conducts output high when both K1 and K2 are energized Output at Y35 conducts output h...

Page 12: ...S11 S12 open S21 S22 closed Check wiring Check switch Ensure connector and wire termination is properly seated Ensure both input channels are open a minimum of 0 5 seconds Power LED ON Fault LED OFF...

Reviews: