E-Stop Safety Module 

– Models ES-UA-5A and ES-VA-5A

Supply Voltage and Current

A1-A: 115V ac (Model ES-UA-5A) or 230V ac (model ES-VA-5A), ± 15%; 50/60Hz 
B1-B: 12-24V dc, ± 15%, 10% max. ripple 
Power consumption: approx. 4W/7VA

Supply Protection Circuitry

Protected against transient voltages and reverse polarity

Output Configuration

Outputs (K1 & K2): four redundant (total of eight) safety relay (forced-guided) contacts – AgNi, 5 µm gold-plated, 
plus 1 N/C Auxiliary Monitor output – AgNi, 5 µm gold-plated
Low Current Rating: 
Caution:  The 5 µm gold-plated contacts allow the switching of low current/low voltage. In these low-

power applications, multiple contacts can also be switched in series (e.g., “dry switching”).

To preserve the gold plating on the contacts, the following max. values should not be exceeded at any time: 
 

Min. voltage: 1V ac/dc 

 

Max. voltage: 60V 

 

Min. current: 5 mA ac/dc 

 

Max. current: 300 mA 

 

Min. power: 5 mW (5 mVA)   

Max. power: 7 W (7 VA)

High Current Rating: 
If higher loads must be switched through one or more of the contacts, the minimum and maximum values of the 
contact(s) changes to: 
 

Min. voltage: 15V ac/dc 

 

Max. voltage: 250V ac/dc 

 

Min. current: 250 mA ac/dc   

Max. current: 6 A 

 

Min. power: 5 W (5 VA) 

 

Max. power: 200 W (1500 VA)

Mechanical life: 50,000,000 operations 
Electrical life:  150,000 operations (typical, @ 1,500 VA switched power, resistive load) 

150,000 operations (typical, @ 200 W switched power, resistive load)

NOTE:  Transient suppression is recommended when switching inductive loads. Install suppressors 

across load. Never install suppressors across output contacts (see Warning, page 6).

Solid-State Monitor Outputs: 
Two non-safety solid-state dc outputs 
Output at Y32 monitors state of outputs – conducts (output high) when both K1 and K2 are energized 
Output at Y35 conducts (output high) when internal power supply is OK 
Output circuits require application of +12-24V dc ± 15% at terminal Y31; dc common at Y30 
Maximum switching current: 100 mA at 12-24V dc 
Both outputs are protected against short circuits

Output Response Time

25 milliseconds typical

Input Requirements

E-stop switch must have normally closed contacts each capable of switching 20 to 50mA @ 12 to 30V dc;  
and must be open ≥ 10 ms for a valid stop command. Maximum input resistance 250 Ω per channel. 
Reset switch must have one normally open contact capable of switching 20 to 50mA @ 12 to 30V dc. 

On-Time Delay

100 ms; time from the E-stop contacts to close (Auto Reset) or the reset button to open (Manual Reset) and the 
safety outputs to close.

Status Indicators

 green LED indicators:  Power ON, K1 energized, K2 energized 
1 red LED indicator responds to fault of internal power supply, ground fault, or cross-short of input channels (see 
“Troubleshooting” on back cover for LED condition descriptions).

Housing

Polycarbonate. Rated NEMA 1 (IEC IP20)

Mounting

Mounts to standard 35 mm DIN rail track. Safety Module must be installed inside an enclosure rated NEMA 3  
(IEC IP54), or better.

Vibration Resistance

10 to 55Hz @ 0.35 mm displacement per IEC 68-2-6

Operating Conditions

Operating Temperature: 0° to +50° C (+32° to 122° F) 
Maximum Relative Humidity: 90% @ +50° C (non-condensing) 
Heat Dissipation Considerations: See page 5

Dimensions

See Figure 7, page 10

Certifications

Specifications

EMERGENCY STOP DEVICE

29YL

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for ES-UA-5A

Page 1: ...FPA 79 and IEC EN 60204 1 6 amp safety output contacts Plug in terminal blocks 12 24V dc 115V ac or 12 24V dc 230V ac operation External Device Monitoring one channel EDM WARNING This Emergency Stop S...

Page 2: ...tion are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are followed U S Standards Applicable...

Page 3: ...nnels each of which is the series connection of two forced guided relay contacts that are internally monitored K1 and K2 in Figures 4 and 5 If the Module detects a failure such as a welded output rela...

Page 4: ...these possibilities physically separate the wires from each other and from other sources of power e g in separate wireways or conduit According to the definition of European standard EN 954 1 a 1 cha...

Page 5: ...multitude of machine control configurations The following guidelines are general in nature The ES UA 5A and ES VA 5A Modules have no delay function Their output relay contacts open within 25 milliseco...

Page 6: ...utput dc common V 12 24V dc Y32 Y35 Jumper For power connection see Figure 6 Reset Switch MSC2 MSC3 MSC4 E Stop Switch Figure 4 Hookup 2 Channel E Stop Applications WARNING Wiring of Arc Suppressors I...

Page 7: ...S35 Arc Suppressors see WARNING on page 6 6A max K1D K2D 43 44 6A max K1E K2E 51 52 Non safety Auxiliary Monitor Contact Y31 Y30 Non safety Monitor Outputs 20mA max each Output Outputs Energized Powe...

Page 8: ...ES VA 5A may be used also with automatic reset If no MSC monitor contacts are monitored a jumper must be installed between terminals S31 and S32 see Figures 4 and 5 The E Stop Safety Module will reset...

Page 9: ...wiring Return to step 2 after the cause of the problem has been corrected 7 Close the enclosure Apply power to the Machine Control Elements and perform the Periodic Checkout Procedure NOTE If more tha...

Page 10: ...escription of the problem If they conclude that a component is defective they will issue an RMA Return Merchandise Authorization number for your paperwork and give you the proper shipping address 2 Pa...

Page 11: ...page 6 Solid State Monitor Outputs Two non safety solid state dc outputs Output at Y32 monitors state of outputs conducts output high when both K1 and K2 are energized Output at Y35 conducts output h...

Page 12: ...S11 S12 open S21 S22 closed Check wiring Check switch Ensure connector and wire termination is properly seated Ensure both input channels are open a minimum of 0 5 seconds Power LED ON Fault LED OFF...

Reviews: