Example: Change Universal Input 2 to a 0 to 10 V dc Input
1. Write a 3 to Modbus register 3326 on Modbus Slave ID 11 (I/O board).
2. Cycle power to the device.
3. Using the
Register View
tab, read register 3326 to verify it is set to 3.
Example: Change Analog Output 1 to a 0 to 10 V dc Output
1. Change the
Source Register
selection to
I/O Board Registers
.
2. Set jumper 1 on the I/O base board to the 0 to 10 V position. Refer to the base board image for the analog output
jumper position.
3. Write a 3 to Modbus register 4008 on Modbus Slave ID 11 (I/O board).
4. Cycle power to the device.
5. Using the
Register View
tab, read register 4008 to verify it is set to 3.
4.4.2 NMOS Outputs for the DXM100
Table 2: NMOS output pins for the DXM100 models
Pin
NMOS Discrete
Outputs
Modbus Register
Description
Wiring
22
4
504
Less than 1 A maximum current at 30 V DC
ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
Output
23
3
503
24
2
502
35
1
501
4.4.3 Analog (DAC) Outputs for the B2 and S2 Models
The B2 and S2 analog outputs are 0 to 10 V dc outputs and cannot be changed.
DXM100/1000-B2 and S2 Models
Pin
Analog
Output
Modbus
Register
Description
20
1
509
0 to 10 V dc output
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
19
2
510
4.4.4 DC Latching Outputs for the B2 and S2 Models
Pin
DC Latching Outputs
Modbus Register
Description
Wiring
9
D1A
507
Write a 1 to the output register to activate the DC
Latching output from A to B.
Write a 0 to the output register to deactivate the DC
Latching output form B to A.
DB
DA
2-wire
self-latching
solenoid
10
D1B
11
D2A
508
12
D2B
The DXM Configuration Software allows the user to adjust parameters that govern the operation of the DC latch outputs.
Most applications will not require any changes for correct operation. Software parameters include:
•
Enable H-Bridge
—Enable or disable the H-bridge output. Default Enabled.
•
Voltage
—The voltage applied to the output when the output is activated. Default 13 V dc.
•
Cap Warmup Time
—The amount of time given to charge the output capacitor. The more time given to charge the
output capacitor the more energy will be available to turn on the output. Default 80 ms
•
Switch Time
—The amount of time the output is turned on to be able to change the solenoid output. Default 40 ms
Sure Cross
®
DXM100-Sx Wireless Modbus Slave
20
www.bannerengineering.com - Tel: + 1 888 373 6767