3. Enter a site name.
4. Click 

Create

.

The Gateway/Site appears in the listing of devices on the Gateways screen.

5. Click 

Edit Gateway

 (pencil icon) next to your Gateway/Site name.

The Gateway detail window appears.

6. Copy the 

Site ID

 number located at the top of this window.

The Site ID number created by the web server is a required parameter in the configuration of the DXM. The Site ID is
the address the webserver uses to store the data pushed from the DXM.

7. Click 

Save

.

5.2.3 Modifying the XML Configuration File

Use the DXM Configuration Software to configure the operation of the DXM.
Launch the software. You can use one of these three screens to modify registers:

Local Registers

—Edits individual registers

Modify Multiple Registers

—Edits multiple registers at the same time

Local Registers in Use

—Edits individual registers

Refer to the 

DXM Configuration Software Instruction Manual

 (p/n 209933) for more details.

5.2.4 Configure the Cloud Data Services Settings

1. To configure the connection to the web server, go to the 

Settings

 > 

Cloud Services

 screen.

 

 

2. Copy and paste the 

Site ID

.

The Site ID is that long string of numbers and letters from the Banner Cloud Data Services website.

3. Verify the 

Server Name/IP

 is set to 

push.bannercds.com

 and the 

Page

 is set to 

/push.aspx

 for sending to the

website.

4. Set the 

Cloud Push Interval

 to a value appropriate for your application.

The 

Cloud Push Interval

 determines how often the device pushes the data to the web. The faster the push interval,

the more data is sent to the site. Cellular plans can only push at an interval of 10 minutes or longer. The 

Sample

Count

 specifies how many times the data is gathered within the 

Cloud Push Interval

.

For example, if the 

Cloud Push Interval

 is 15 minutes and the 

Sample Count

 is set to 3, then during each data push

(every 15 minutes), 3 samples are sent to the web. This is one sample every 5 minutes.

5. Set the 

Push Method

 to 

HTTP Cloud Push

 and the 

Push Interface

 to 

Cell

.

6. On the 

Cellular

 screen, select the appropriate 

Cell Module

.

Select 

SXI-CATM1VZW-001

 for kit model numbers ending in 

-V

Select 

SXI-CATM1ATT-001

 for kit model numbers ending in 

-A

The 

APN

 will automatically change accordingly.

7. Save the configuration file by going to 

File

 > 

Save

.

File names must be no more than 30 characters long, and should not contain any spaces or special characters.

8. With a USB cable connected to the device, go to the 

Device

 > 

Connection Settings

 menu.

 

 

DXM Enclosure Kit (DEK) Series

 

www.bannerengineering.com - Tel: + 1 888 373 6767

17

Summary of Contents for DXM Series

Page 1: ...DXM Enclosure Kit DEK Series Instruction Manual Original Instructions 223953 Rev A 20 July 2021 Banner Engineering Corp All rights reserved 223953...

Page 2: ...Node to a DXM and Assign the Node Address 13 4 3 3 Conduct a Site Survey from the DXM 14 5 Activating Services 15 5 1 Banner Cellular Data Services 15 5 1 1 Activate Cell Services 15 5 1 2 Create an...

Page 3: ...ations typically isolated from traditional infrastructure A five watt solar panel delivers a nominal 12 V DC standard output built with a heavy duty anodized frame and rugged design for withstanding h...

Page 4: ...ord grips into locations 3 and 4 4 Install the smallest cable gland PG7 for the solar cable at location 2 2 2 Wire the Battery The battery and DXM ship from the factory pre mounted to the DIN rail 1 I...

Page 5: ...g cleat with the arc facing out Convex orientation b Leave the hardware a little loose so that the bracket can slide onto the panel frame between the mating surfaces c Move the cleat to the center of...

Page 6: ...p until it clicks closed 3 Wire the solar panel to the DXM Figure 5 Solar panel wiring to the DXM a Feed the cable from the solar panel to the DXM through the small cable gland b Connect the brown lea...

Page 7: ...eraging trending and thresholding Low complexity solutions SMS text message Notifications Email Notifications Push data on conditions Text Programming Language ScriptBasic Medium complexity solutions...

Page 8: ...1 1 1 1 1 1 LED2 TB1 C6 R82 TB4 P2 P4 SW1 C4 P5 SW2 P10 TB3 P7 TB2 TB9 Y1 P6 L2 TB5 TVS1 L1 R77 P9 P8 P1 LED1 P3 A B C D G H J K L 1 18 19 32 M L Pin Name Description 1 No Connection Not used 2 PW 12...

Page 9: ...registers 503 1A maximum at 30 V DC 24 N2 NMOS OUT 2 NMOS switch to ground controlled by I O Modbus registers 502 1A maximum at 30 V DC 25 N1 NMOS OUT 1 NMOS switch to ground controlled by I O Modbus...

Page 10: ...minute intervals Two DC latching outputs toggling every 5 minutes One temperature humidity probe powered from 16 V switched power reading every 5 minutes ScriptBasic program controlling temperature h...

Page 11: ...isters Local Registers in Use screen The bottom status bar displays the communications status application status and the DXM Configuration Software version In this short example we will configure the...

Page 12: ...e to display the parameters 3 Name your rule 4 Select the slave ID 5 Select how many registers to read and the beginning register 6 Define the register type how often to read the register and any othe...

Page 13: ...P switch 4 back OFF and cycle power again to return to normal operation of the XML and script Adjust the XML or script to slow down the RTU read or write rules Upload a blank XML bind all devices then...

Page 14: ...site survey on a DX80 network does not affect the throughput of the DX80 network The DX80 Gateway Node system can run a site survey analysis while the network is operational For a MulitHop network the...

Page 15: ...ellular data opening screen 3 Select the region the system is operating in If the system is within the contiguous United States select United States from the region drop down list If the system will b...

Page 16: ...ed to the cellular network 5 2 Banner Cloud Data Services BannerCDS 5 2 1 Activate Cloud Services Follow these instructions to activate your cloud services account 1 Go to the bannercds com website 2...

Page 17: ...nner Cloud Data Services website 3 Verify the Server Name IP is set to push bannercds com and the Page is set to push aspx for sending to the website 4 Set the Cloud Push Interval to a value appropria...

Page 18: ...esent your specific kit After the XML file is loaded into the webserver the webserver uses the register names and configurations defined in the configuration file 5 Click on the Site Name link to go t...

Page 19: ...d from the enclosure 6 Use the included screws to fasten the plate to the enclosure Do not over torque 7 Use the 2 13 16 to 3 3 4 pole clamps and the geometry of the plate tabs to fasten the enclosure...

Page 20: ...ensure no ground loops are created No surge suppressor can absorb all lightning strikes do not touch the Sure Cross device or any equipment connected to the Sure Cross device during a thunderstorm Ex...

Page 21: ...ANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UN...

Page 22: ...modify 17 save 13 upload 13 upload to website 18 configure cloud settings 17 create new site 16 M modify configuration file 17 multiple registers 11 registers 17 R registers multiple registers 11 S sa...

Reviews: