Setup Mode
Use Setup mode to change sensor output response for:
• Light or Dark operate
• 30-millisecond pulse stretcher (OFF-delay), if required
• 200 s high-speed response
If Setup mode configuration is interrupted and remains inactive for 60 sec-
onds, the sensor returns to Run mode with the most recent settings (i.e.,
exits and saves current selection).
Setup mode operates in the “background,” while the outputs are active;
changes are updated instantly.
Setup status
indicators
Press and hold both
buttons for more than
2 seconds to access
Setup Mode
Push Button
0.04 seconds < "Click" < 0.8
seconds
Remote Line
0.04 seconds < T < 0.8 seconds
Result
Access Setup
Mode
• Press and hold both push but-
tons > 2 seconds
• Double-pulse remote line
T
T
T
Power LED: OFF
Output LED: remains active
Icon continue to display current setup
Static LEDs: OFF
Select Setting
Combination
• Click either push button until
LEDs show desired settings.
or
• Pulse the remote line until
LEDs show desired settings.
NOTE: Double-pulsing the remote
line will cause the setting to "back
up" one step.
Sensor toggles through eight setting combinations, in the
following order:
LO - Normal Speed - No Delay (default)
DO - Normal Speed - No Delay
LO - High Speed - No Delay
DO - High Speed - No Delay
LO - Normal Speed - Delay
DO - Normal Speed - Delay
LO - High Speed - Delay
DO - High Speed - Delay
Return to Run
Mode
• Press and hold both push but-
tons > 2 seconds
• Hold remote line low > 2 sec-
onds.
2 seconds
Power LED: ON
Sensor returns to RUN mode with new settings.
D10 Expert Series with Bar Graph Display and Discrete Output
8