Technical data
4.6.1.2 Grounding
Caution!
The functional ground (ground connection)
must be connected to the central grounding
point (e.g. control cabinet or system) via the
shortest possible path with the lowest possi-
ble resistance and with the largest possible wire
cross section. This type of grounding is manda-
tory for proper functionality.
For example, a copper strip must be attached to the ground connection at a central grounding point of the control
cabinet or system in which the device is installed. The wire cross section should be as large as possible (at least
2.5 mm²).
4.6.1.3 Ethernet interfaces
The PPC1200 is equipped with 2 externally routed Eth-
ernet interfaces.
Information:
For all Ethernet connections, only connections within a building are permitted, taking into account
maximum lengths.
ETH1, ETH2
Variant
RJ45, female
Controller
Intel I210
Wiring
S/STP (Cat 5e)
Transfer rate
10/100/1000 Mbit/s
1)
Cable length
Max. 100 m (min. Cat 5e)
LED "Speed" (a)
On
Off
Green
100 Mbit/s
10 Mbit/s
2)
Orange (dark)
1000 Mbit/s
-
LED "Link" (b)
On
Active
Orange (light)
Link (a connection to an
Ethernet network exists)
Blinking (data be-
ing transferred)
1)
Switching takes place automatically.
2)
The 10 Mbit/s transfer rate / connection is only available if LED "Link" is active at the same time.
A special driver is required to operate the Ethernet controller. Drivers for approved operating systems are available
for download in the Downloads section of the B&R website (
) (if required and not already
included in the operating system).
Information:
Necessary drivers must be downloaded from the B&R website, not from manufacturer websites.