Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
3.7.2 Add-on RS232/422/485 interface - 5AC600.485I-00
The serial interface is a combined RS232/RS422/RS485 interface. The operating mode
(RS232/RS422/RS485) is selected automatically, depending on the electrical connection.
Pin assignments
I/O address and IRQ
Figure 76: Add-on RS232/422/485 interface - 5AC600.485I-00
Add-on RS232/422/485
Features
RS232
RS422/485
9-pin DSUB connector
Type
RS232 not modem compatible;
Electrically isolated
UART
16550 compatible, 16 byte FIFO
Transfer rate
Max. 115 kBit/s
Bus length
Max. 15 meters
Max. 1200 meters
Pin
Assignments
(RS232)
Assignments
(RS422)
1
n.c.
TXD\
2
RXD
n.c.
3
TXD
n.c.
4
n.c.
TXD
5
GND
GND
6
n.c.
RXD\
7
RTS
n.c.
8
CTS
n.c.
9
n.c.
RXD
Table 90: Pin assignments - RS232/RS422
Resource
Default setting
Additional setting options
I/O address
2E8
238, 2F8, 338, 3E8, 3F8
IRQ
IRQ10
IRQ 3, 4, 5, 7, 11, 12
Table 91: Add-on RS232/422/485 - I/O address and IRQ