Technical data • Individual components
44
Automation PC 510 User's Manual V 1.01
3.4.4 5PP5IF.FPLM-00
General information
The interface board 5PP5IF.FPLM-00 has two POWERLINK connections and 512 kB SRAM.
The integrated hub allows for the easiest possible implementation of a simple tree structure or optional ring-redun-
dancy without extra effort.
With pollresponse chaining, the module also offers a solution for the highest demands in regard to response time
and the shortest cycle times. When combined with the B&R control system, poll response chaining provides ideal
performance, particularly for central control tasks.
•
2x POWERLINK V1/V2 connections
•
512 KB SRAM
•
Integrated hub for efficient cabling
•
Configurable ring redundancy
•
Poll response chaining
•
Compatible with PP500, APC510, APC511
The interface board can only be operated under Automation Runtime.
Order data
Model number
Short description
Image
Interface boards
5PP5IF.FPLM-00
PP500 interface board; connections for 2x POWERLINK (with
integrated hub); 512 kB SRAM.
Table 33: 5PP5IF.FPLM-00 - Order data
Technical data
Product ID
5PP5IF.FPLM-00
General information
B&R ID code
$B4D8
Diagnostics
Data transfer
Yes, with status LED
Certification
CE
Yes
Controllers
SRAM
Size
512 kB
Battery-buffered
Yes
Interfaces
POWERLINK
Amount
2
Transmission
100 Base-T (ANSI/IEEE 802.3)
Type
Type 4
Design
Internal 2x hub, 2x shielded RJ45 port
Transfer rate
100 Mbit/s
Cable length
Max. 100 m between two stations (segment length)
Electrical properties
Power consumption
3 W
Environmental conditions
Temperature
Operation
0 to 55°C
Storage
-20 to 60°C
Transport
-20 to 60°C
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Table 34: 5PP5IF.FPLM-00 - Technical data