5
ELECTRICAL CONNECTIONS
To guarantee the safety of operator and to prevent damages to components, while caring out the connections or inserting
the radio receiver, the control unit must be disconnected from electric feeding.
For feeding cables, motors lines, lines for blinker/ courtesy light, electric lock use a cable with appropriate section to the length of the connection
(min 1,5mmq). For auxiliary feedings of commands and the safety contacts, use minimum section of 0.5mmq. In case those cables are too long
(beyond 30m), it’s better to do a decoupling by setting up relays on the control unit.
In case of intervention of a fuse, after removing the problem, change it by another with the same characteristics.
Install safety devices, limit switches, photocells, rubber edges and Stop pushbutton.
If one or more safety devices are not installed, short-circuit the relative clamps with the common of the commands.
All contacts N.C. dress to the same input must be connected in series.
All contacts N.A. dress to the same input must be connected in parallel.
Preview disconnecting devices on the feeding line in an accessible place. For the feeding of the control unit set an appropriate external discon-
necting device (not included with equipment
Hold the cables of feeding separated from those of the encoder with a distance between motor and control unit of maximum 10m. Don’t use
multi pole cables.
Functioning of the Electric lock output, ELS: connect it between clamp N.10 and clamp N.11 –when an opening command is given, 1s of switch-
ing on is executed before the activation of M1
Functioning of flashing light: connect it between clamp N.11 and clamp N.12, maximum power 25W 24Vdc. In opening and in closing, it execute
a forewarn of 1,5s to signal that the automation is starting the movement.
Functioning of “phototest” on the feeding of photocell TX: if you want to execute a phototest cycle on every opening, set Dip 8 = ON and connect
the NEGATIVE feeding of the photocell emitter to clamp N.13
CONNECTION OF MOTORS ELECTRIC FEEDING
Motor M1 : connect between clamp N.6 and clamp N.7
Motor M2 : connect between clamp N.8 and clamp N.9 – Motor M2 in closing, start first.